Specifications

Brand Siemens
Model 6ES7422-1BL00-0AA0
Order Number 6ES7422-1BL00-0AA0
Digital outputs 32xDC24V/0.5A
Depth 210 mm
Width 25 mm
Height 290 mm
Weight, approx 600 g
Power loss, typ 4 W
Load voltage rated value 24 V
Supply voltage type DC
Diagnostics function No
Isolation tested with 500 V AC/707 V DC, type test
Short-circuit protection Yes; Clocked electronically
Cable length shielded, max 1 000 m
Controlling a digital input Yes; possible
Number of digital outputs 32
Cable length unshielded, max 600 m
Input current from backplane bus 5 V DC, max 200 mA
Load resistance range lower limit 48 Ω
Load resistance range upper limit 4 kΩ
Output voltage for signal "1", min L+ (-0.3) V
Output current for signal "1", rated value 0.5 A
Input current from load voltage L+ (without load), max 30 mA
Load voltage permissible range lower limit 20.4 V
Load voltage permissible range upper limit 28.8 V
Switching capacity on lamp load, max 5 W
Switching frequency with inductive load, max 0.5 Hz
Switching frequency on lamp load, max 10 Hz
Switching frequency with resistive load, max 100 Hz
Output current for signal "0", residual current, max 0.3 mA
Short-circuit response threshold, typ 0.7 to 1.5 A
Limitation of inductive shutdown voltage to -27 V
Potential separation digital outputs between the channels No
Switching frequency with inductive load (acc. to IEC 60947-5-1, DC13), max 2 Hz; 2 Hz at 0.3 A; 0.5 Hz at 0.5 A
Output delay with resistive load, "0" to "1", max 1 ms
Output delay with resistive load, "1" to "0", max 1 ms
Output current for signal "1", permissible range, max 0.6 A
Output current for signal "1", permissible range, min 5 mA
Parallel switching of two outputs for uprating Yes; possible (only outputs of the same group)
Parallel switching of two outputs for redundant control of a load Yes; possible (only outputs of the same group)
Potential separation between the channels and backplane bus Yes
Total current of the outputs (per group), all mounting positions up to 40 °C, max 4 A
Total current of the outputs (per group), all mounting positions up to 60 °C, max 2 A; 8 adjacent outputs each
Potential separation between the channels, in groups of 32