跳至主要内容

Phoenix Contact QUINT-PS/1AC/24DC/5/CO 2320908 电源模块 - 二手

Phoenix Contact QUINT-PS/1AC/24DC/5/CO 2320908 电源模块 - 二手

询价

填写数量、期望成色和目的地。

获取报价

说明

Phoenix Contact QUINT-PS/1AC/24DC/5/CO 二手电源模块,支持 AC 100-240 V 输入和 DC 24 V 输出。

规格参数

Brand Phoenix Contact
Model QUINT-PS/1AC/24DC/5/CO
Order Number 2320908
HS Code 850440
Origin Thailand
Voltage 10 V (Test Level 3)
AC frequency range 45 Hz ... 65 Hz
Continuous load current ≤ 20 mA
Inrush current < 15 A
Maximum inrush current 20 mA (short-circuit-proof)
Maximum switching voltage 30 V AC
展开其余 195 项规格参数
Nominal output voltage 24 V DC ±1 %
Operational Voltage 85-264 V~ / 90–410 VDC +5% (UL508: 250 V)
POWER BOOST (I Boost ) 7.5 A (-25 °C ... 40 °C permanent, U OUT = 24 V DC )
Power loss nominal load max. 15 W
Voltage type of supply voltage AC
Frequency range 80 MHz ... 1 GHz
Input voltage range 85 V AC ... 264 V AC
Nominal input voltage range 100 V AC ... 240 V AC
Switching voltage range 18 V DC ... 24 V DC
Temperature Range -40...+70°C (>+60°C/+140°F Derating)
Degree of protection IP20
Recommended breaker for input protection 6 A ... 16 A (AC: Characteristics B, C, D, K)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation) 15 Hz ... 150 Hz, 2.3g, 90 min.
DeviceNet approval DeviceNet™ Power Supply Conformance Tested
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise emission EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EMC requirements for noise immunity EN 61000-6-2
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Shipbuilding approval DNV (EMC A)
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Approval - requirement of the semiconductor industry with regard to mains voltage dips SEMI F47-0706 Compliance Certificate
Certificate DNV 19.0188 X
Certificate TÜV 11 ATEX 555674 X
Certificate IECEx TUN 11.0002X
Climatic class 3K22 (in accordance with EN 60721-3-3)
CO2e kg 30.706 kg CO2e
Color green
Color yellow
Comments Criterion A
Conductor cross-section AWG max. 12
Conductor cross-section AWG min. 20
Conductor cross-section flexible max. 2.5 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section, rigid max. 2.5 mm²
Conductor cross-section, rigid min. 0.2 mm²
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Connection method Screw connection
Contact discharge 8 kV (Test Level 4)
Continuous load current 1 A
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 2 % (change in load, dynamic 10 % ... 90 %)
Control deviation < 0.1 % (change in input voltage ±10 %)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Csa CAN/CSA-C22.2 No. 60950-1-07
CSA CSA-C22.2 No. 107.1-01
Current consumption 1.5 A (100 V AC)
Current consumption 0.6 A (240 V AC)
Current consumption 1.3 A (110 V DC)
Current consumption 0.55 A (250 V DC)
Date 2022
Degree of pollution 2
Depth 125 mm
Depth 43 mm
Derating 60 °C ... 70 °C (2.5 %/K)
Discharge current to PE < 3.5 mA
Discharge in air 15 kV (Test Level 4)
ECLASS-13.0 27040701
ECLASS-15.0 27040701
Efficiency typ. 88.3 % (120 V AC)
Efficiency typ. 90 % (230 V AC)
Electric strength, max. 300 V AC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Environment friendly use period (EFUP) EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC002540
Exemption 7(a), 7(c)-I
Explosive atmosphere EN 60079-0
Explosive atmosphere EN 60079-7
Explosive atmosphere EN 60079-15
Feedback voltage resistance ≤ 35 V DC
Frequency range 1 GHz ... 6 GHz
Frequency range 0.15 MHz ... 80 MHz
Frequency range DC 0 Hz
Fulfills EU RoHS substance requirements Yes
Fuse protection (secondary side) electronic
Fuse protection (secondary side) thermal-magnetic
Fuse protection (secondary side) thermal
HART FSK Physical Layer Test Specification Compliance Output voltage U Out compliant
Height 130 mm
Hood version Galvanized sheet steel, free from chrome (VI)
Housing material Metal
Identification Ex ec nC IIC T4 Gc
Identification  II 3 G Ex ec nC IIC T4 Gc
Input 4 kV (Test Level 4 - asymmetrical)
Input 2 kV (Test Level 3 - symmetrical)
Input fuse 5 A (slow-blow, internal)
Input voltage range 110 V DC ... 250 V DC -18 % ... +64 % (UL 508: ≤ 250 V DC)
Input/output/signal asymmetrical
Inrush current integral (I 2 t) < 1 A 2 s
Inrush current limitation 15 A
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Insulation voltage input/output 4 kV AC (type test)
Insulation voltage input/output 2 kV AC (routine test)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Magnetic circuit breaker tripping B2 / B4 / C2
Mains buffering time typ. 55 ms (120 V AC)
Mains buffering time typ. 55 ms (230 V AC)
Max. permissible relative humidity (operation) 100 % (at 25 °C, non-condensing)
Maximum altitude ≤ 5000 m
Maximum inrush current 0.5 A (ATEX/IECEx: Ohmic loads only)
Maximum inrush current 1 A (ATEX/IECEx: Ohmic loads only)
Maximum no-load power dissipation 3 W
Maximum switching voltage 24 V DC
Minimum order quantity 1 pc
Mounting position horizontal DIN rail NS 35, EN 60715
Mounting type DIN rail mounting
MTBF (IEC 61709, SN 29500) > 1134000 h (25 °C)
MTBF (IEC 61709, SN 29500) > 635000 h (40 °C)
Nominal input voltage range 110 V DC ... 250 V DC
Nominal output current (I N ) 5 A (-25 °C ... 60 °C, U OUT = 24 V DC)
Nominal power consumption 141 VA
Noxious gas test ISA-S71.04-1985 G3 Harsh Group A
Number of phases 1
Output 2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
Output description U OUT > 0.9 x U N : High signal
Output description Relay contact, U OUT > 0.9 x U N : Contact closed
Output description I OUT < I N : High signal
Output power 120 W
Output power 180 W
Output voltage + 24 V DC
Overvoltage category (EN 61010-1) II (≤ 5000 m)
Overvoltage category (EN 62477-1) III (≤ 2000 m)
Packing unit 1 pc
PE 3.5 kV AC (type test)
PE 850 V DC (routine test)
PE 2 kV AC (routine test)
Permissible backup fuse B6 B10 B16 AC:
Product key CMPQ13
Product type Power supply
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Protection class I
Protective circuit Transient surge protection; Varistor
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Rail applications EN 50121-4
Rail applications EN 50121-3-2
Rail applications EN 50124-1
Rail applications EN 50155
Residual ripple < 40 mV PP (with nominal values)
Rise time < 0.1 s (U OUT (10 % ... 90 %))
Scip fbca597d-2ac2-4ff0-9b8b-f31fbf969bb0
Screw thread M3
Selective Fuse Breaking (I SFB ) 30 A (12 ms)
Setting range of the output voltage (U Set ) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Side element version Aluminum
Signal 2 kV (Test Level 4 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Siq CB-Scheme (IEC 62368-1, IEC 61010-1, IEC 61010-2-201)
Standard - Electrical safety IEC 61010-2-201 (SELV)
Standard - Equipment safety BG (design tested)
Standard - Safe isolation IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1
Standard designation Fire protection in rail vehicles
Standard designation Safety extra-low voltage
Standard designation Protective extra-low voltage
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standards/regulations EN 55011 (EN 55022)
Standards/regulations EN 61000-4-2
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Standards/regulations EN 61000-4-5
Standards/regulations EN 61000-4-6
Standards/regulations EN 61000-6-3
Standards/specifications EN 45545-2 (HL3)
Standards/specifications IEC 61010-1 (SELV)
Standards/specifications IEC 61010-2-201 (PELV)
Status display U OUT > 0.9 x U N : "DC OK" LED green
Status display I OUT > I N : LED "BOOST" yellow
Stripping length 7 mm
Temperature code T4 (-40 ... +60 °C)
Test field strength 20 V/m (Test Level 3)
Test field strength 10 V/m (Test Level 3)
Tightening torque max 0.6 Nm
Tightening torque, min 0.5 Nm
Types of signaling LED
Types of signaling Active switching output
Types of signaling Relay contact
Typical response time < 0.15 s
UL approvals UL/C-UL listed UL 508
UL approvals UL/C-UL Recognized UL 60950-1
UL approvals UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UNSPSC 21.0 39121000
Voltage type of supply voltage DC
Weight per piece (excluding packing) 777 g
Weight per piece (including packing) 1,081.3 g
Width 40 mm
Width 122 mm
With protective coating yes