| Nominal output voltage |
24 V DC ±1 %
|
| Operational Voltage |
85-264 V~ / 90–410 VDC +5% (UL508: 250 V)
|
| POWER BOOST (I Boost ) |
7.5 A (-25 °C ... 40 °C permanent, U OUT = 24 V DC )
|
| Power loss nominal load max. |
15 W
|
| Voltage type of supply voltage |
AC
|
| Frequency range |
80 MHz ... 1 GHz
|
| Input voltage range |
85 V AC ... 264 V AC
|
| Nominal input voltage range |
100 V AC ... 240 V AC
|
| Switching voltage range |
18 V DC ... 24 V DC
|
| Temperature Range |
-40...+70°C (>+60°C/+140°F Derating)
|
| Degree of protection |
IP20
|
| Recommended breaker for input protection |
6 A ... 16 A (AC: Characteristics B, C, D, K)
|
| Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
|
| Vibration (operation) |
15 Hz ... 150 Hz, 2.3g, 90 min.
|
| DeviceNet approval |
DeviceNet™ Power Supply Conformance Tested
|
| EMC requirements for noise emission |
EN 61000-6-3
|
| EMC requirements for noise emission |
EN 61000-6-4
|
| EMC requirements for noise immunity |
EN 61000-6-1
|
| EMC requirements for noise immunity |
EN 61000-6-2
|
| REACH candidate substance (CAS No.) |
Lead (CAS: 7439-92-1)
|
| Shipbuilding approval |
DNV (EMC A)
|
| Ambient temperature (operation) |
-40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
|
| Ambient temperature (storage/transport) |
-40 °C ... 85 °C
|
| Approval - requirement of the semiconductor industry with regard to mains voltage dips |
SEMI F47-0706 Compliance Certificate
|
| Certificate |
DNV 19.0188 X
|
| Certificate |
TÜV 11 ATEX 555674 X
|
| Certificate |
IECEx TUN 11.0002X
|
| Climatic class |
3K22 (in accordance with EN 60721-3-3)
|
| CO2e kg |
30.706 kg CO2e
|
| Color |
green
|
| Color |
yellow
|
| Comments |
Criterion A
|
| Conductor cross-section AWG max. |
12
|
| Conductor cross-section AWG min. |
20
|
| Conductor cross-section flexible max. |
2.5 mm²
|
| Conductor cross-section flexible min. |
0.2 mm²
|
| Conductor cross-section, rigid max. |
2.5 mm²
|
| Conductor cross-section, rigid min. |
0.2 mm²
|
| Connection in parallel |
yes, for redundancy and increased capacity
|
| Connection in series |
yes
|
| Connection method |
Screw connection
|
| Contact discharge |
8 kV (Test Level 4)
|
| Continuous load current |
1 A
|
| Control deviation |
< 1 % (change in load, static 10 % ... 90 %)
|
| Control deviation |
< 2 % (change in load, dynamic 10 % ... 90 %)
|
| Control deviation |
< 0.1 % (change in input voltage ±10 %)
|
| Criterion A |
Normal operating behavior within the specified limits.
|
| Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself.
|
| Csa |
CAN/CSA-C22.2 No. 60950-1-07
|
| CSA |
CSA-C22.2 No. 107.1-01
|
| Current consumption |
1.5 A (100 V AC)
|
| Current consumption |
0.6 A (240 V AC)
|
| Current consumption |
1.3 A (110 V DC)
|
| Current consumption |
0.55 A (250 V DC)
|
| Date |
2022
|
| Degree of pollution |
2
|
| Depth |
125 mm
|
| Depth |
43 mm
|
| Derating |
60 °C ... 70 °C (2.5 %/K)
|
| Discharge current to PE |
< 3.5 mA
|
| Discharge in air |
15 kV (Test Level 4)
|
| ECLASS-13.0 |
27040701
|
| ECLASS-15.0 |
27040701
|
| Efficiency |
typ. 88.3 % (120 V AC)
|
| Efficiency |
typ. 90 % (230 V AC)
|
| Electric strength, max. |
300 V AC
|
| Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU
|
| Emitted radio interference in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential
|
| Environment friendly use period (EFUP) |
EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| ETIM 10.0 |
EC002540
|
| Exemption |
7(a), 7(c)-I
|
| Explosive atmosphere |
EN 60079-0
|
| Explosive atmosphere |
EN 60079-7
|
| Explosive atmosphere |
EN 60079-15
|
| Feedback voltage resistance |
≤ 35 V DC
|
| Frequency range |
1 GHz ... 6 GHz
|
| Frequency range |
0.15 MHz ... 80 MHz
|
| Frequency range DC |
0 Hz
|
| Fulfills EU RoHS substance requirements |
Yes
|
| Fuse protection (secondary side) |
electronic
|
| Fuse protection (secondary side) |
thermal-magnetic
|
| Fuse protection (secondary side) |
thermal
|
| HART FSK Physical Layer Test Specification Compliance |
Output voltage U Out compliant
|
| Height |
130 mm
|
| Hood version |
Galvanized sheet steel, free from chrome (VI)
|
| Housing material |
Metal
|
| Identification |
Ex ec nC IIC T4 Gc
|
| Identification |
II 3 G Ex ec nC IIC T4 Gc
|
| Input |
4 kV (Test Level 4 - asymmetrical)
|
| Input |
2 kV (Test Level 3 - symmetrical)
|
| Input fuse |
5 A (slow-blow, internal)
|
| Input voltage range |
110 V DC ... 250 V DC -18 % ... +64 % (UL 508: ≤ 250 V DC)
|
| Input/output/signal |
asymmetrical
|
| Inrush current integral (I 2 t) |
< 1 A 2 s
|
| Inrush current limitation |
15 A
|
| Installation distance right/left |
5 mm / 5 mm
|
| Installation distance top/bottom |
50 mm / 50 mm
|
| Insulation voltage input/output |
4 kV AC (type test)
|
| Insulation voltage input/output |
2 kV AC (routine test)
|
| Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC
|
| Magnetic circuit breaker tripping |
B2 / B4 / C2
|
| Mains buffering time |
typ. 55 ms (120 V AC)
|
| Mains buffering time |
typ. 55 ms (230 V AC)
|
| Max. permissible relative humidity (operation) |
100 % (at 25 °C, non-condensing)
|
| Maximum altitude |
≤ 5000 m
|
| Maximum inrush current |
0.5 A (ATEX/IECEx: Ohmic loads only)
|
| Maximum inrush current |
1 A (ATEX/IECEx: Ohmic loads only)
|
| Maximum no-load power dissipation |
3 W
|
| Maximum switching voltage |
24 V DC
|
| Minimum order quantity |
1 pc
|
| Mounting position |
horizontal DIN rail NS 35, EN 60715
|
| Mounting type |
DIN rail mounting
|
| MTBF (IEC 61709, SN 29500) |
> 1134000 h (25 °C)
|
| MTBF (IEC 61709, SN 29500) |
> 635000 h (40 °C)
|
| Nominal input voltage range |
110 V DC ... 250 V DC
|
| Nominal output current (I N ) |
5 A (-25 °C ... 60 °C, U OUT = 24 V DC)
|
| Nominal power consumption |
141 VA
|
| Noxious gas test |
ISA-S71.04-1985 G3 Harsh Group A
|
| Number of phases |
1
|
| Output |
2 kV (Test Level 3 - asymmetrical)
|
| Output |
1 kV (Test Level 2 - symmetrical)
|
| Output description |
U OUT > 0.9 x U N : High signal
|
| Output description |
Relay contact, U OUT > 0.9 x U N : Contact closed
|
| Output description |
I OUT < I N : High signal
|
| Output power |
120 W
|
| Output power |
180 W
|
| Output voltage |
+ 24 V DC
|
| Overvoltage category (EN 61010-1) |
II (≤ 5000 m)
|
| Overvoltage category (EN 62477-1) |
III (≤ 2000 m)
|
| Packing unit |
1 pc
|
| PE |
3.5 kV AC (type test)
|
| PE |
850 V DC (routine test)
|
| PE |
2 kV AC (routine test)
|
| Permissible backup fuse |
B6 B10 B16 AC:
|
| Product key |
CMPQ13
|
| Product type |
Power supply
|
| Protection against overvoltage at the output (OVP) |
≤ 32 V DC
|
| Protection class |
I
|
| Protective circuit |
Transient surge protection; Varistor
|
| Radio interference voltage in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential
|
| Rail applications |
EN 50121-4
|
| Rail applications |
EN 50121-3-2
|
| Rail applications |
EN 50124-1
|
| Rail applications |
EN 50155
|
| Residual ripple |
< 40 mV PP (with nominal values)
|
| Rise time |
< 0.1 s (U OUT (10 % ... 90 %))
|
| Scip |
fbca597d-2ac2-4ff0-9b8b-f31fbf969bb0
|
| Screw thread |
M3
|
| Selective Fuse Breaking (I SFB ) |
30 A (12 ms)
|
| Setting range of the output voltage (U Set ) |
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
|
| Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
| Side element version |
Aluminum
|
| Signal |
2 kV (Test Level 4 - asymmetrical)
|
| Signal |
1 kV (Test Level 2 - asymmetrical)
|
| Siq |
CB-Scheme (IEC 62368-1, IEC 61010-1, IEC 61010-2-201)
|
| Standard - Electrical safety |
IEC 61010-2-201 (SELV)
|
| Standard - Equipment safety |
BG (design tested)
|
| Standard - Safe isolation |
IEC 61010-2-201
|
| Standard - safety for equipment for measurement, control, and laboratory use |
IEC 61010-1
|
| Standard designation |
Fire protection in rail vehicles
|
| Standard designation |
Safety extra-low voltage
|
| Standard designation |
Protective extra-low voltage
|
| Standard – Limitation of mains harmonic currents |
EN 61000-3-2
|
| Standards/regulations |
EN 55011 (EN 55022)
|
| Standards/regulations |
EN 61000-4-2
|
| Standards/regulations |
EN 61000-4-3
|
| Standards/regulations |
EN 61000-4-4
|
| Standards/regulations |
EN 61000-4-5
|
| Standards/regulations |
EN 61000-4-6
|
| Standards/regulations |
EN 61000-6-3
|
| Standards/specifications |
EN 45545-2 (HL3)
|
| Standards/specifications |
IEC 61010-1 (SELV)
|
| Standards/specifications |
IEC 61010-2-201 (PELV)
|
| Status display |
U OUT > 0.9 x U N : "DC OK" LED green
|
| Status display |
I OUT > I N : LED "BOOST" yellow
|
| Stripping length |
7 mm
|
| Temperature code |
T4 (-40 ... +60 °C)
|
| Test field strength |
20 V/m (Test Level 3)
|
| Test field strength |
10 V/m (Test Level 3)
|
| Tightening torque max |
0.6 Nm
|
| Tightening torque, min |
0.5 Nm
|
| Types of signaling |
LED
|
| Types of signaling |
Active switching output
|
| Types of signaling |
Relay contact
|
| Typical response time |
< 0.15 s
|
| UL approvals |
UL/C-UL listed UL 508
|
| UL approvals |
UL/C-UL Recognized UL 60950-1
|
| UL approvals |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
|
| UNSPSC 21.0 |
39121000
|
| Voltage type of supply voltage |
DC
|
| Weight per piece (excluding packing) |
777 g
|
| Weight per piece (including packing) |
1,081.3 g
|
| Width |
40 mm
|
| Width |
122 mm
|
| With protective coating |
yes
|