Phoenix Contact UNO2-PS/1AC/24DC/480W fonte de alimentação
Descricao
Phoenix Contact UNO2-PS/1AC/24DC/480W integra a linha UNO POWER como fonte de alimentação. Fornece saída nominal de 24 V DC. O produto é montado em trilho DIN e tem grau de proteção IP20.
Especificacoes
| Brand | Phoenix Contact |
|---|---|
| Model | UNO2-PS/1AC/24DC/480W |
| Order Number | 2910105 |
| HS Code | 850440 |
| Voltage | 10 V (Test Level 3) |
| Frequency | 50 Hz |
| Inrush current | typ. 15 A (at 25 °C) |
| Nominal output voltage | 24 V DC |
| Power loss nominal load max. | < 28 W (230 V AC) |
| Switching voltage | max. 30 V AC/DC |
| Typical national grid voltage | 120 V AC |
| Voltage type of supply voltage | AC |
| Frequency range | 0 kHz ... 2 kHz |
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
| Nominal input voltage range | 100 V AC ... 240 V AC |
| Degree of protection | IP20 |
| Depth (Device depth (DIN rail mounting)) | 125 mm (Device depth (DIN rail mounting)) |
| Integrated fuse protection | no |
| Recommended breaker for input protection | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Vibration (operation) | 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6) |
| Vibration (operation) | 50 Hz ... 150 Hz, 2.3g, 90 min. |
| EMC requirements for noise immunity | EN 61000-6-2 |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
| Additional text | 120 V AC |
| Additional text | 230 V AC |
| Additional text | Test Level 2 |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Awg | 24 ... 10 (Cu) |
| Climatic class | 3K22 (in accordance with EN 60721) |
| CO2e kg | 37.414 kg CO2e |
| Color | green |
| Comments | Criterion A |
| Comments | Criterion B |
| Connection in parallel | yes, for redundancy |
| Connection in series | yes, for increased output voltage |
| Connection method | Screw connection |
| Contact discharge | 6 kV (Test Level 3) |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Control deviation | < 3 % (change in load, dynamic 10 % ... 90 %) |
| Control deviation | < 0.1 % (change in input voltage ±10 %) |
| Crest factor | typ. 1.667 (120 V AC) |
| Crest factor | typ. 1.75 (230 V AC) |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Current carrying capacity | max. 50 mA |
| Current consumption | 5.4 A (100 V AC) |
| Current consumption | 4.4 A (120 V AC) |
| Current consumption | 2.3 A (230 V AC) |
| Current consumption | 2.2 A (240 V AC) |
| Degree of pollution | 2 |
| Depth | 129 mm |
| Derating | < 90 V AC (1 %/V) |
| Derating | 55 °C ... 70 °C |
| Device mains fuse | 8 A internal (device protection), fast-blow |
| Discharge current to PE | < 3.5 mA |
| Discharge in air | 8 kV (Test Level 3) |
| Drive form screw head | Slotted L |
| ECLASS-13.0 | 27040701 |
| ECLASS-15.0 | 27040701 |
| Efficiency | typ. 93 % (120 V AC) |
| Efficiency | typ. 94.6 % (230 V AC) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Environment friendly use period (EFUP) | EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. |
| Environmental protection directive | RoHS Directive 2011/65/EU |
| Environmental protection directive | WEEE |
| Environmental protection directive | Reach |
| ETIM 10.0 | EC002540 |
| Exemption | 7(a), 7(c)-I |
| Feedback voltage resistance | ≤ 35 V DC |
| Flammability rating according to UL 94 | V0 (Housing, terminal blocks) |
| Flexible | 0.2 mm² ... 4 mm² |
| flexible with ferrule with plastic sleeve | 0.25 mm² ... 4 mm² |
| flexible with ferrule without plastic sleeve | 0.25 mm² ... 4 mm² |
| Foot latch material | Sheet steel, zinc-plated |
| Frequency range | 80 MHz ... 1 GHz |
| Frequency range | 1 GHz ... 6 GHz |
| Frequency range | 0.15 MHz ... 80 MHz |
| Frequency range (f N ) | 50 Hz ... 60 Hz ±10 % |
| Fulfills EU RoHS substance requirements | Yes |
| Function | Visual operating state display |
| Function | Operating state forwarding |
| Fuse protection (secondary side) | electronic |
| Fuse protection (secondary side) | thermal-magnetic |
| Fuse protection (secondary side) | thermal |
| Height | 130 mm |
| Hood version | Stainless steel |
| Housing material | Metal |
| Housing material | Aluminum (AlMg3) / sheet steel, zinc-plated |
| Identification | 1.1 (), 1.2 (L), 1.3 (N) |
| Identification | 2.1, 2.2 (+), 2.3, 2.4 (-) |
| Identification | 3.1 (13), 3.2 (14) |
| Identification | UL/C-UL Listed UL 61010-1 |
| Identification | UL/C-UL Listed UL 61010-2-201 |
| Identification | UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
| Identification | CB scheme (IEC 61010-1, IEC 61010-2-201) |
| Input | 4 kV (Test Level 4 - asymmetrical) |
| Input | 2 kV (Test Level 4 - symmetrical) |
| Input/Output | asymmetrical |
| Inrush current integral (I 2 t) | < 1 A 2 s |
| Installation distance right/left (active, passive) | 0 mm / 0 mm |
| Installation distance top/bottom (active, passive) | 30 mm / 30 mm |
| Insulation voltage input/output | 4 kV AC (type test) |
| Insulation voltage input/output | 3 kV AC (routine test) |
| Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
| LED off | Supply voltage input AC not present (Off) |
| LED on (flashing green) DC OK < 0.9 x UN | U OUT < 0,9 x U N (on (flashing green)) |
| LED on (green), DC OK | U OUT > 0,9 x U N (On (green), DC OK) |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Mains buffering time | typ. 17 ms (120 V AC) |
| Mains buffering time | typ. 18 ms (230 V AC) |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum altitude | ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m) |
| Maximum no-load power dissipation | < 3 W (230 V AC) |
| Minimum no-load power dissipation | < 2.9 W (120 V AC) |
| Minimum nominal load power dissipation | < 37 W (120 V AC) |
| Minimum order quantity | 1 pc |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Mounting type | DIN rail mounting |
| MTBF (IEC 61709, SN 29500) | > 900000 h (25 °C) |
| MTBF (IEC 61709, SN 29500) | > 530000 h (40 °C) |
| MTBF (IEC 61709, SN 29500) | > 280000 h (55 °C) |
| No-load proof | yes |
| Nominal output current (I N ) | 20 A |
| Nominal power consumption | 533 VA |
| Number of periods | 25 / 30 periods |
| Number of periods | 12 periods |
| Number of periods | 1 period |
| Number of phases | 1 |
| Output | 2 kV (Test Level 3 - asymmetrical) |
| Output | 1 kV (Test Level 3 - symmetrical) |
| Output power (P N ) | 480 W |
| Overvoltage category (EN 61010-1) | II (≤ 3000 m) |
| Overvoltage category (EN 62477-1) | III (≤ 3000 m) |
| Packing unit | 1 pc |
| PE | 3.5 kV AC (type test) |
| PE | 2.4 kV AC (routine test) |
| Position | 1.x |
| Position | 2.x |
| Position | 3.x |
| Position marking | 3.1 (13), 3.2 (14) |
| Product key | CMPV13 |
| Product type | Power supply |
| Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
| Protection class | I |
| Protective circuit | Transient surge protection; Varistor, gas-filled surge arrester |
| Residual ripple | typ. 70 mV PP (with nominal values) |
| Rigid | 0.2 mm² ... 6 mm² |
| rigid (AWG) | 24 ... 10 (Cu) |
| Rise time | < 1 s (U Out = 10 % ... 90 %) |
| Scip | 73c1ec9c-e95e-4452-8f4b-8bfe396d6c7e |
| Setting range of the output voltage (U Set ) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
| Shock (operation) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
| Short-circuit-proof | yes |
| Side element version | Aluminum |
| Standard designation | Electrical safety |
| Standard designation | Safety for equipment for measurement, control, and laboratory use |
| Standard designation | Protective extra-low voltage |
| Standard designation | Safe isolation |
| Standard designation | Limitation of harmonic line currents |
| Standard designation | Requirement of the semiconductor industry with regard to mains voltage dips |
| Standards/regulations | EN 55016 |
| Standards/regulations | EN 61000-6-3 (Class B) |
| Standards/regulations | EN 61000-3-2 |
| Standards/regulations | EN 61000-3-2 (Class A) |
| Standards/regulations | EN 61000-3-3 |
| Standards/regulations | EN 61000-4-2 |
| Standards/regulations | EN 61000-4-3 |
| Standards/regulations | EN 61000-4-4 |
| Standards/regulations | EN 61000-4-5 |
| Standards/regulations | EN 61000-4-6 |
| Standards/regulations | EN 61000-4-11 |
| Standards/specifications | DIN EN 61558-2-16 |
| Standards/specifications | IEC 61010-2-201 (SELV) |
| Standards/specifications | IEC 61010-1 |
| Standards/specifications | IEC 61010-1 (SELV) |
| Standards/specifications | IEC 61010-2-201 (PELV) |
| Standards/specifications | IEC 61558-2-16 |
| Standards/specifications | IEC 61010-2-201 |
| Standards/specifications | EN 61000-3-2 |
| Standards/specifications | SEMI F47 - 0706 (180 V AC) |
| State condition (Contact closed) | U OUT > 0,9 x U N (Contact closed) |
| State condition (Contact open) | U OUT < 0,9 x U N (Contact open) |
| Stripping length | 8 mm |
| Supply system configuration | Star network (TN, TT, IT (PE)) |
| Switch contact (floating) | OptoMOS |
| Switch-on time | typ. 1 s |
| Switching voltage | max. 60 V DC |
| Temperature | 40 °C |
| Temperature | 25 °C |
| Temperature code | T4 (-25°C ... +70°C; >55°C, derating: 2.5 %/K) |
| Test field strength | 10 V/m (Test Level 3) |
| Tightening torque () | 4 lb f -in. ... 5 lb f -in. |
| Tightening torque (EU) | 0.5 Nm ... 0.6 Nm |
| Type of signaling | DC OK switch contact - signal state operation (U N = 24 V DC, I Out = I N ) |
| Types of signaling | LED DC OK - signal state operation (U N = 24 V DC, I Out = I N ) |
| Typical national grid voltage | 230 V AC |
| UNSPSC 21.0 | 39121000 |
| Voltage | 230 V AC |
| Voltage dip | 70 % |
| Voltage dip | 40 % |
| Voltage dip | 0 % |
| Weight per piece (excluding packing) | 1,084 g |
| Weight per piece (including packing) | 1,252.4 g |
| Width | 59 mm |
| With protective coating | no |