コンテンツへスキップ

Phoenix Contact UNO2-PS/1AC/24DC/480W 電源装置

Phoenix Contact UNO2-PS/1AC/24DC/480W 電源装置

見積もりを依頼

数量、希望状態、配送先を入力してください。

見積もりを依頼

説明

Phoenix Contact UNO2-PS/1AC/24DC/480W は UNO POWER シリーズの電源装置です。 定格出力は 24 V DC です。 DIN レールに取り付けられます。保護等級は IP20 です。

仕様

Brand Phoenix Contact
Model UNO2-PS/1AC/24DC/480W
Order Number 2910105
HS Code 850440
Voltage 10 V (Test Level 3)
Frequency 50 Hz
Inrush current typ. 15 A (at 25 °C)
Nominal output voltage 24 V DC
Power loss nominal load max. < 28 W (230 V AC)
Switching voltage max. 30 V AC/DC
Typical national grid voltage 120 V AC
Voltage type of supply voltage AC
Frequency range 0 kHz ... 2 kHz
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Nominal input voltage range 100 V AC ... 240 V AC
Degree of protection IP20
Depth (Device depth (DIN rail mounting)) 125 mm (Device depth (DIN rail mounting))
Integrated fuse protection no
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Vibration (operation) 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6)
Vibration (operation) 50 Hz ... 150 Hz, 2.3g, 90 min.
EMC requirements for noise immunity EN 61000-6-2
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Additional text 120 V AC
Additional text 230 V AC
Additional text Test Level 2
Ambient temperature (operation) -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Awg 24 ... 10 (Cu)
Climatic class 3K22 (in accordance with EN 60721)
CO2e kg 37.414 kg CO2e
Color green
Comments Criterion A
Comments Criterion B
Connection in parallel yes, for redundancy
Connection in series yes, for increased output voltage
Connection method Screw connection
Contact discharge 6 kV (Test Level 3)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (change in load, dynamic 10 % ... 90 %)
Control deviation < 0.1 % (change in input voltage ±10 %)
Crest factor typ. 1.667 (120 V AC)
Crest factor typ. 1.75 (230 V AC)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Current carrying capacity max. 50 mA
Current consumption 5.4 A (100 V AC)
Current consumption 4.4 A (120 V AC)
Current consumption 2.3 A (230 V AC)
Current consumption 2.2 A (240 V AC)
Degree of pollution 2
Depth 129 mm
Derating < 90 V AC (1 %/V)
Derating 55 °C ... 70 °C
Device mains fuse 8 A internal (device protection), fast-blow
Discharge current to PE < 3.5 mA
Discharge in air 8 kV (Test Level 3)
Drive form screw head Slotted L
ECLASS-13.0 27040701
ECLASS-15.0 27040701
Efficiency typ. 93 % (120 V AC)
Efficiency typ. 94.6 % (230 V AC)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Environment friendly use period (EFUP) EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
Environmental protection directive RoHS Directive 2011/65/EU
Environmental protection directive WEEE
Environmental protection directive Reach
ETIM 10.0 EC002540
Exemption 7(a), 7(c)-I
Feedback voltage resistance ≤ 35 V DC
Flammability rating according to UL 94 V0 (Housing, terminal blocks)
Flexible 0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve 0.25 mm² ... 4 mm²
flexible with ferrule without plastic sleeve 0.25 mm² ... 4 mm²
Foot latch material Sheet steel, zinc-plated
Frequency range 80 MHz ... 1 GHz
Frequency range 1 GHz ... 6 GHz
Frequency range 0.15 MHz ... 80 MHz
Frequency range (f N ) 50 Hz ... 60 Hz ±10 %
Fulfills EU RoHS substance requirements Yes
Function Visual operating state display
Function Operating state forwarding
Fuse protection (secondary side) electronic
Fuse protection (secondary side) thermal-magnetic
Fuse protection (secondary side) thermal
Height 130 mm
Hood version Stainless steel
Housing material Metal
Housing material Aluminum (AlMg3) / sheet steel, zinc-plated
Identification 1.1 (), 1.2 (L), 1.3 (N)
Identification 2.1, 2.2 (+), 2.3, 2.4 (-)
Identification 3.1 (13), 3.2 (14)
Identification UL/C-UL Listed UL 61010-1
Identification UL/C-UL Listed UL 61010-2-201
Identification UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Identification CB scheme (IEC 61010-1, IEC 61010-2-201)
Input 4 kV (Test Level 4 - asymmetrical)
Input 2 kV (Test Level 4 - symmetrical)
Input/Output asymmetrical
Inrush current integral (I 2 t) < 1 A 2 s
Installation distance right/left (active, passive) 0 mm / 0 mm
Installation distance top/bottom (active, passive) 30 mm / 30 mm
Insulation voltage input/output 4 kV AC (type test)
Insulation voltage input/output 3 kV AC (routine test)
Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
LED off Supply voltage input AC not present (Off)
LED on (flashing green) DC OK < 0.9 x UN U OUT < 0,9 x U N (on (flashing green))
LED on (green), DC OK U OUT > 0,9 x U N (On (green), DC OK)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Mains buffering time typ. 17 ms (120 V AC)
Mains buffering time typ. 18 ms (230 V AC)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Maximum altitude ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Maximum no-load power dissipation < 3 W (230 V AC)
Minimum no-load power dissipation < 2.9 W (120 V AC)
Minimum nominal load power dissipation < 37 W (120 V AC)
Minimum order quantity 1 pc
Mounting position horizontal DIN rail NS 35, EN 60715
Mounting type DIN rail mounting
MTBF (IEC 61709, SN 29500) > 900000 h (25 °C)
MTBF (IEC 61709, SN 29500) > 530000 h (40 °C)
MTBF (IEC 61709, SN 29500) > 280000 h (55 °C)
No-load proof yes
Nominal output current (I N ) 20 A
Nominal power consumption 533 VA
Number of periods 25 / 30 periods
Number of periods 12 periods
Number of periods 1 period
Number of phases 1
Output 2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
Output power (P N ) 480 W
Overvoltage category (EN 61010-1) II (≤ 3000 m)
Overvoltage category (EN 62477-1) III (≤ 3000 m)
Packing unit 1 pc
PE 3.5 kV AC (type test)
PE 2.4 kV AC (routine test)
Position 1.x
Position 2.x
Position 3.x
Position marking 3.1 (13), 3.2 (14)
Product key CMPV13
Product type Power supply
Protection against overvoltage at the output (OVP) ≤ 35 V DC
Protection class I
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Residual ripple typ. 70 mV PP (with nominal values)
Rigid 0.2 mm² ... 6 mm²
rigid (AWG) 24 ... 10 (Cu)
Rise time < 1 s (U Out = 10 % ... 90 %)
Scip 73c1ec9c-e95e-4452-8f4b-8bfe396d6c7e
Setting range of the output voltage (U Set ) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Shock (operation) 18 ms, 30g, per spatial direction (IEC 60068-2-27)
Short-circuit-proof yes
Side element version Aluminum
Standard designation Electrical safety
Standard designation Safety for equipment for measurement, control, and laboratory use
Standard designation Protective extra-low voltage
Standard designation Safe isolation
Standard designation Limitation of harmonic line currents
Standard designation Requirement of the semiconductor industry with regard to mains voltage dips
Standards/regulations EN 55016
Standards/regulations EN 61000-6-3 (Class B)
Standards/regulations EN 61000-3-2
Standards/regulations EN 61000-3-2 (Class A)
Standards/regulations EN 61000-3-3
Standards/regulations EN 61000-4-2
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Standards/regulations EN 61000-4-5
Standards/regulations EN 61000-4-6
Standards/regulations EN 61000-4-11
Standards/specifications DIN EN 61558-2-16
Standards/specifications IEC 61010-2-201 (SELV)
Standards/specifications IEC 61010-1
Standards/specifications IEC 61010-1 (SELV)
Standards/specifications IEC 61010-2-201 (PELV)
Standards/specifications IEC 61558-2-16
Standards/specifications IEC 61010-2-201
Standards/specifications EN 61000-3-2
Standards/specifications SEMI F47 - 0706 (180 V AC)
State condition (Contact closed) U OUT > 0,9 x U N (Contact closed)
State condition (Contact open) U OUT < 0,9 x U N (Contact open)
Stripping length 8 mm
Supply system configuration Star network (TN, TT, IT (PE))
Switch contact (floating) OptoMOS
Switch-on time typ. 1 s
Switching voltage max. 60 V DC
Temperature 40 °C
Temperature 25 °C
Temperature code T4 (-25°C ... +70°C; >55°C, derating: 2.5 %/K)
Test field strength 10 V/m (Test Level 3)
Tightening torque () 4 lb f -in. ... 5 lb f -in.
Tightening torque (EU) 0.5 Nm ... 0.6 Nm
Type of signaling DC OK switch contact - signal state operation (U N = 24 V DC, I Out = I N )
Types of signaling LED DC OK - signal state operation (U N = 24 V DC, I Out = I N )
Typical national grid voltage 230 V AC
UNSPSC 21.0 39121000
Voltage 230 V AC
Voltage dip 70 %
Voltage dip 40 %
Voltage dip 0 %
Weight per piece (excluding packing) 1,084 g
Weight per piece (including packing) 1,252.4 g
Width 59 mm
With protective coating no