コンテンツへスキップ

Phoenix Contact TRIO-PS-2G/1AC/24DC/20 電源装置

Phoenix Contact TRIO-PS-2G/1AC/24DC/20 電源装置

見積もりを依頼

数量、希望状態、配送先を入力してください。

見積もりを依頼

説明

Phoenix Contact TRIO-PS-2G/1AC/24DC/20 は TRIO POWER シリーズの電源装置です。 DIN レールに取り付けられます。保護等級は IP20 です。

仕様

Brand Phoenix Contact
Model TRIO-PS-2G/1AC/24DC/20
Order Number 2903151
HS Code 850440
Voltage 10 V (Test Level 3)
AC frequency range 50 Hz ... 60 Hz ±10 %
Continuous load current 100 mA
Inrush current ≤ 20 A (typical)
Nominal output voltage 24 V DC ±1 %
Power factor (UMax) > 0.9 (230 V AC)
Power factor (UMin) > 0.9 (120 V AC)
Power loss nominal load max. < 44.8 W (120 V AC)
Power loss nominal load max. < 36.8 W (230 V AC)
Shut-down voltage < 77 V DC
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Switch-on voltage ≥ 87 V DC
Typical national grid voltage 120 V AC
Voltage type of supply voltage AC
Frequency range Class A, B
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Nominal input voltage range 100 V AC ... 240 V AC
Degree of protection IP20
Recommended breaker for input protection 10 A ... 16 A (Characteristics B, C, D, K)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation) 15 Hz ... 150 Hz, 4g, 90 min.
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise emission EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EMC requirements for noise immunity EN 61000-6-2
REACH candidate substance (CAS No.) Diboron trioxide (CAS: 1303-86-2)
REACH candidate substance (CAS No.) Lead monoxide (lead oxide) (CAS: 1317-36-8)
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Shipbuilding approval DNV GL
13/14 U OUT > 0.9 x U N (U N = 24 V DC)
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
CO2e kg 37.31 kg CO2e
Color green
Comments Criterion A
Comments Criterion B
Conductor cross-section AWG max. 12
Conductor cross-section AWG max. 8
Conductor cross-section AWG max. 16
Conductor cross-section AWG min. 24
Conductor cross-section flexible max. 2.5 mm²
Conductor cross-section flexible max. 6 mm²
Conductor cross-section flexible max. 1.5 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section, rigid max. 4 mm²
Conductor cross-section, rigid max. 10 mm²
Conductor cross-section, rigid max. 1.5 mm²
Conductor cross-section, rigid min. 0.2 mm²
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Connection method Push-in connection
Contact discharge 6 kV (Test Level 4)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Control deviation < 0.1 % (change in input voltage ±10 %)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Current consumption 5.6 A (100 V AC)
Current consumption 4.3 A (120 V AC)
Current consumption 2.4 A (230 V AC)
Current consumption 2.4 A (240 V AC)
Current consumption 4.9 A (110 V DC)
Current consumption 2.1 A (250 V DC)
DC OK U OUT > 0.9 x U N (U N = 24 V DC)
Default closed
Degree of pollution 2
Depth 160 mm
Derating > 60 °C ... 70 °C (2.5 %/K)
Digital 30 V AC 30 V DC 100 mA
Discharge current to PE < 3.5 mA
Discharge in air 8 kV (Test Level 4)
Dynamic Boost (I Dyn.Boost ) 30 A (5 s)
ECLASS-13.0 27040701
ECLASS-15.0 27040701
Efficiency typ. 91.4 % (120 V AC)
Efficiency typ. 92.9 % (230 V AC)
Electric strength, max. ≤ 300 V AC 15 s
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Environment friendly use period (EFUP) EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC002540
Exemption 7(a), 7(c)-I
Extended input voltage range in operation > 99 V DC
Feedback voltage resistance ≤ 35 V DC
Frequency range 0 kHz ... 2 kHz
Frequency range 80 MHz ... 1 GHz
Frequency range 1 GHz ... 2 GHz
Frequency range 2 GHz ... 3 GHz
Frequency range 0.15 MHz ... 80 MHz
Fulfills EU RoHS substance requirements Yes
Height 130 mm
Hood version Polycarbonate
Housing material Metal
Input 4 kV (Test Level 4 - asymmetrical)
Input 3 kV (Test Level 3 - symmetrical)
Input 6 kV (Test Level 4 - asymmetrical)
Input fuse 10 A (internal (device protection))
Input voltage range 110 V DC ... 250 V DC ±10 %
Input/Output asymmetrical
Inrush current integral (I 2 t) < 0.9 A 2 s
Inrush current limitation typ. 20 A (after 1 ms)
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Insulation voltage input/output 3 kV AC (type test)
Insulation voltage input/output 1.5 kV AC (routine test)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Mains buffering time typ. 10 ms (120 V AC)
Mains buffering time typ. 15 ms (230 V AC)
Mains buffering time > 15 ms (230 V AC)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Maximum altitude ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Maximum no-load power dissipation < 2.9 W (120 V AC)
Maximum no-load power dissipation < 2.8 W (230 V AC)
Minimum order quantity 1 pc
Mounting position horizontal DIN rail NS 35, EN 60715
Mounting type DIN rail mounting
MTBF (IEC 61709, SN 29500) > 1800000 h (25 °C)
MTBF (IEC 61709, SN 29500) > 1000000 h (40 °C)
MTBF (IEC 61709, SN 29500) > 480000 h (60 °C)
Network type Star network
No-load proof yes
Nominal input voltage range 110 V DC ... 250 V DC
Nominal output current (I N ) 20 A
Nominal power consumption 534.7 VA
Number of phases 1
Output 2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
Output 2 kV (Test Level 1 - asymmetrical)
Output characteristic U/I with dynamic load reserve
Output power 480 W
Output power 720 W (5 s)
Overvoltage category (EN 62368-1) II (≤ 2000 m)
Packing unit 1 pc
Product key CMPO13
Product type Power supply
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Protection class I (in closed control cabinet)
Protective circuit Transient surge protection; Varistor
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Rail applications EN 50121-4
Residual ripple < 100 mV PP (with nominal values)
Rise time 20 ms (U OUT (10 % ... 90 %))
Scip 02d6fdba-a12f-4e6b-9800-f398bba1e238
Setting range of the output voltage (U Set ) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Short-circuit-proof yes
Signal 1 kV (Test Level 2 - asymmetrical)
Signalization designation DC OK
SIL in accordance with IEC 61508 0
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, max. 6 mm²
Single conductor/terminal point, stranded, with ferrule, max. 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Standard - Electrical safety IEC 62368-1 (SELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standards/regulations EN 55016
Standards/regulations EN 61000-6-3 (Class B)
Standards/regulations EN 55011 (EN 55022)
Standards/regulations EN 61000-4-2
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Standards/regulations EN 61000-4-5
Standards/regulations EN 61000-4-6
Standards/regulations EN 61000-6-3
Status display LED
Stripping length 10 mm
Stripping length 15 mm
Stripping length 8 mm
terminal blocks) V0
Test field strength 10 V/m (Test Level 3)
Type of housing Aluminum (AlMg3)
Types of signaling LED
Types of signaling Floating signal contact
Typical national grid voltage 230 V AC
Typical response time < 1 s
UL approvals UL Listed UL 508
UL approvals UL/C-UL Recognized UL 60950-1
UL approvals UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
UNSPSC 21.0 39121000
Voltage type of supply voltage DC
Weight per piece (excluding packing) 1,321.8 g
Weight per piece (including packing) 1,539.1 g
Width 68 mm
With protective coating no