コンテンツへスキップ

Phoenix Contact QUINT4-PS/1AC/12DC/7.5/PT 電源装置

Phoenix Contact QUINT4-PS/1AC/12DC/7.5/PT 電源装置

見積もりを依頼

数量、希望状態、配送先を入力してください。

見積もりを依頼

説明

Phoenix Contact QUINT4-PS/1AC/12DC/7.5/PT は QUINT POWER シリーズの電源装置です。 定格出力は 12 V DC です。 DIN レールに取り付けられます。保護等級は IP20 です。

仕様

Brand Phoenix Contact
Model QUINT4-PS/1AC/12DC/7.5/PT
Order Number 2904607
Voltage 10 V (Test Level 3)
Frequency 16.67 Hz
Current 7.5 A
Inrush current typ. 11.4 A (at 25 °C)
Nominal output voltage 12 V DC
Power loss nominal load max. < 8.1 W (120 V AC)
Power loss nominal load max. < 7.1 W (230 V AC)
Standard – Safety extra-low voltage IEC 61010-1 (SELV)
Typical national grid voltage 120 V AC
Voltage type of supply voltage AC
Switching frequency 4.00 kHz ... 70.00 kHz (Auxiliary converter stage)
Frequency range 0 kHz ... 2 kHz
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Degree of protection IP20
Recommended breaker for input protection 6 A ... 16 A (Characteristic B, C or comparable)
Vibration (operation) < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6)
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise emission EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EMC requirements for noise immunity EN 61000-6-2
EMC requirements for power supply IEC 61850-3 (G,H)
EMC requirements for power supply EN 61000-6-5 (switching devices)
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Additional text 120 V AC
Additional text 230 V AC
Additional text 60 s
Additional text 3 s
Additional text DC, 60 s
Additional text Test Level 2
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
CO2e kg 10.764 kg CO2e
Comments Criterion A
Comments Criterion B
Conductor cross-section AWG max. 14
Conductor cross-section AWG min. 24
Conductor cross-section flexible max. 2.5 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section, rigid max. 2.5 mm²
Conductor cross-section, rigid min. 0.2 mm²
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Connection method Push-in connection
Contact discharge 8 kV (Test Level 4)
Control deviation < 0.3 % (Static load change 10 % ... 90 %)
Control deviation < 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Control deviation < 0.1 % (change in input voltage ±10 %)
Crest factor typ. 1.57 (120 V AC)
Crest factor typ. 1.67 (230 V AC)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Current consumption 1 A (100 V AC)
Current consumption 0.85 A (120 V AC)
Current consumption 0.46 A (230 V AC)
Current consumption 0.44 A (240 V AC)
Current consumption 0.92 A (110 V DC)
Current consumption 0.4 A (250 V DC)
Default 12 V DC 24 mA 12 V DC for U Out > 0.9 x U Set
Degree of pollution 2
Depth 90 mm
Digital 0 V DC 12 V DC 24 mA
Discharge current to PE < 0.25 mA (264 V AC, 60 Hz)
Discharge current to PE < 0.17 mA
Discharge in air 15 kV (Test Level 4)
Dynamic Boost (I Dyn.Boost ) 12.75 A (≤ 60 °C (5 s))
ECLASS-13.0 27040701
ECLASS-15.0 27040701
Efficiency typ. 91.5 % (120 V AC)
Efficiency typ. 92.5 % (230 V AC)
Electric strength, max. 300 V AC 60 s
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
ETIM 10.0 EC002540
Exemption 7(a), 7(c)-I
Feedback voltage resistance ≤ 25 V DC
Frequency 50 Hz
Frequency 60 Hz
Frequency 0 Hz
Frequency range 80 MHz ... 1 GHz
Frequency range 1 GHz ... 6 GHz
Frequency range 0.15 MHz ... 80 MHz
Frequency range 50 Hz ... 60 Hz
Frequency range (f N ) 50 Hz ... 60 Hz -10 % ... +10 %
Fulfills EU RoHS substance requirements Yes
Fuse protection (secondary side) electronic
Height 106 mm
Hood version Polycarbonate
Housing material Plastic
Input 4 kV (Test Level 4 - asymmetrical)
Input 2 kV (Test Level 4 - symmetrical)
Input 2 kV (symmetrical)
Input 4 kV (asymmetrical)
Input fuse 3.15 A (slow-blow, internal)
Input voltage range 110 V DC ... 250 V DC -20 % ... +40 %
Input/output/signal asymmetrical
Inrush current integral (I 2 t) < 0.2 A 2 s
Inrush current limitation < 11.4 A
Installation distance right/left (active) 15 mm / 15 mm (P Out ≥50% )
Installation distance right/left (active, passive) 0 mm / 0 mm (P Out ≤50 %)
Installation distance right/left (passive) 5 mm / 5 mm (P Out ≥50% )
Installation distance top/bottom (active) 30 mm / 30 mm (P Out ≥50% )
Installation distance top/bottom (active, passive) 30 mm / 30 mm (P Out ≤50 %)
Installation distance top/bottom (passive) 30 mm / 30 mm (P Out ≥50% )
Insulation voltage input/output 4 kV AC (type test)
Insulation voltage input/output 3 kV AC (routine test)
Mains buffering time typ. 48 ms (120 V AC)
Mains buffering time typ. 48 ms (230 V AC)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Maximum no-load power dissipation < 0.6 W (230 V AC)
Maximum no-load power dissipation < 0.6 W (120 V AC)
Minimum order quantity 1 pc
Mounting type DIN rail mounting
MTBF (IEC 61709, SN 29500) > 1221000 h (25 °C)
MTBF (IEC 61709, SN 29500) > 671000 h (40 °C)
MTBF (IEC 61709, SN 29500) > 248000 h (60 °C)
No-load proof yes
Nominal output current (I N ) 7.5 A
Nominal power consumption 96.3 VA
Number of periods 0.5 / 1 / 30 periods
Number of periods 5 / 10 / 50 periods
Number of periods 0.5 / 1 / 5 / 50 periods
Number of phases 1
Output 4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Output power 90 W
Output power 150 W
Overvoltage category (EN 61010-1) II (≤ 5000 m)
Overvoltage category (EN 62477-1) III (≤ 2000 m)
P Out > P Thr (LED lights up yellow, output power > P Thr, depending on the rotary selector switch setting)
Packing unit 1 pc
Product key CMPI12
Product type Power supply
Protection against overvoltage at the output (OVP) ≤ 18 V DC
Protection class II
Protective circuit Transient surge protection; Varistor
Residual ripple < 35 mV PP (with nominal values)
Rise time 50 ms (U Out = 10 % ... 90 %)
Scip 0c7ace05-b5de-466f-8ef2-05caf4801fbd
Setting range of the output voltage (U Set ) 12 V DC ... 15 V DC (constant capacity)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Short-circuit-proof yes
Signal 4 kV (Test Level 4 - asymmetrical)
Signal 0.5 kV (Test Level 2 - symmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.25 mm²
Siq CB-Scheme (IEC 61010-1, IEC 61010-2-201)
Standard - Safe isolation IEC 61558-2-16
Standard - Safe isolation IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1
Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-2-201 (SELV)
Standard - Safety of transformers EN 61558-2-16
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Safety extra-low voltage IEC 61010-2-201 (PELV)
Standards/regulations EN 55016
Standards/regulations EN 61000-6-3 (Class B)
Standards/regulations Additional basic standard EN 61000-6-5 (immunity in switching devices), IEC/EN 61850-3 (power supply)
Standards/regulations EN 61000-3-2
Standards/regulations EN 61000-3-2 (Class A)
Standards/regulations EN 61000-3-3
Standards/regulations EN 61000-4-2
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Standards/regulations EN 61000-4-5
Standards/regulations EN 61000-4-6
Standards/regulations EN 61000-4-8
Standards/regulations EN 61000-4-11
Standards/regulations EN 61000-4-9
Standards/regulations EN 61000-4-12
Standards/regulations EN 61000-4-16
Standards/regulations EN 61000-4-18
Stripping length 10 mm
Switching frequency 80.00 kHz ... 190.00 kHz (Main converter stage)
Switching frequency 30.00 kHz ... 150.00 kHz (PFC stage)
Temperature 40 °C
Temperature 25 °C
Temperature code T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K)
terminal blocks) V0
Test field strength 20 V/m (Test Level 3)
Test field strength 10 V/m (Test Level 3)
Test field strength 100 A/m
Test field strength 1 kA/m
Test field strength 300 A/m
Test field strength 1000 A/m
Test level 1 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Test level 2 16.67 Hz 50 Hz 60 Hz (Test Level 2)
Time 96000 h
Time 145000 h
Time 280000 h
Time 430000 h
Type of housing Polycarbonate
Types of signaling LED
Typical national grid voltage 230 V AC
Typical response time 300 ms
U Out > 0.9 x U Set (LED lights up green)
U Out < 0.9 x U Set (LED flashes green)
UL approvals UL Listed UL 61010-1
UL approvals UL Listed UL 61010-2-201
UL approvals UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UNSPSC 21.0 39121000
Voltage 100 V AC
Voltage 30 V (10 s)
Voltage 300 V (1 s)
Voltage 1 kV (symmetrical)
Voltage 2.5 kV (asymmetrical)
Voltage dip 70 %
Voltage dip 40 %
Voltage dip 0 %
Voltage type of supply voltage DC
Weight per piece (excluding packing) 307 g
Weight per piece (including packing) 384.6 g
Width 45 mm
With protective coating no