仕様

Brand B&R
MPN X20 DO 9322
Origin Austria
Nominal output current 0.5 A
Nominal voltage 24 VDC
Switching voltage 24 VDC -15% / +20%
Total nominal current 6 A
Output protection Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current") Internal freewheeling diode for switching inductive loads (see section "Switching inductive loads")
ABS Yes
Additional power dissipation caused by actuators (resistive) [W] +0.63
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
B&R ID code 0x1B9A
Braking voltage when switching off inductive loads Typ. 50 VDC
Bus 0.26 W
BV EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
CCS Yes
CE Yes
Connection type 1-wire connections
CRA (Cyber Resilience Act) In preparation
Diagnostic status Output monitoring with 10 ms delay
Electrical isolation Channel isolated from bus Channel not isolated from channel and I/O power supply
HazLoc cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Horizontal Yes
Horizontal mounting orientation -25 to 60°C
Installation elevation above sea level Reduction of ambient temperature by 0.5°C per 100 m
Installation elevation above sea level No limitation
Installation elevation above sea level IP20
Insulation voltage between channel and bus 500 V eff
Internal I/O 1.15 W
KC Yes
KR Yes
Leakage current when the output is switched off 5 µA
LR ENV1
Module run/error Yes, using LED status indicator and software
Operation 5 to 95%, non-condensing
Output circuit Source
output voltage 24 VDC
Outputs Yes, using LED status indicator and software (output error status)
Pitch 12.5 +0.2 mm
Product Family X20 System
R DS(on) 210 mΩ
Resistive load Max. 500 Hz
Status indicators I/O function per channel, operating state, module status
Storage -40 to 85°C
Storage 5 to 95%, non-condensing
Switch-on in the event of overload shutdown or short-circuit shutdown Approx. 10 ms (depends on the module temperature)
Transport -40 to 85°C
Transport 5 to 95%, non-condensing
UKCA Yes
UL cULus E115267 Industrial control equipment cULus E537419 Engine generator controller
Variant Current-sourcing FET
Vertical Yes
Vertical mounting orientation -25 to 50°C