コンテンツへスキップ

B&R X20 AI 1744 X20システムモジュール - 新品

B&R X20 AI 1744 X20システムモジュール - 新品

見積もりを依頼

必要な内容をお知らせください。在庫状況と価格について折り返しご連絡します。

依頼を開始

説明

B&R X20システムモジュール X20AI1744 Rev F0、オーストリア製。新品在庫、元の梱包付き。

仕様

Brand B&R
Model X20 AI 1744
MPN X20 AI 1744
Origin Austria
Pitch 12.5 +0.2 mm
Storage -40 to 85°C
CE Yes
KC Yes
UL cULus E115267 Industrial control equipment
Input Yes, using LED status indicator and software
Transport -40 to 85°C
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
UKCA Yes
HazLoc cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Bus 0.01 W
Electrical isolation Bus isolated from analog input and strain gauge supply voltage Channel not isolated from I/O power supply
Order 3
Slope 60 dB
Storage 5 to 95%, non-condensing
Open circuit Yes, using LED status indicator and software
Operation 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
B&R ID code 0x1CDE
Full-bridge strain gauge 336 nV
Full-bridge strain gauge 671 nV
Full-bridge strain gauge 1.343 µV
Full-bridge strain gauge 1.31 nV
Full-bridge strain gauge 2.62 nV
Full-bridge strain gauge 5.25 nV
Module run/error Yes, using LED status indicator and software
Full-bridge strain gauge 2.686 µV
Full-bridge strain gauge 5.371 μV
Full-bridge strain gauge 10.74 μV
Full-bridge strain gauge 10.49 nV
Full-bridge strain gauge 20.98 nV
Full-bridge strain gauge 41.96 nV
Full-bridge strain gauge 21.48 μV
Full-bridge strain gauge 42.97 μV
Full-bridge strain gauge 83.92 nV
Full-bridge strain gauge 167.85 nV
Internal I/O 0.5 W
Vertical Yes
Connection 4- or 6-wire connections
Input type Differential, used to evaluate a full-bridge strain gauge
Voltage 5.5 VDC / Max. 65 mA
Status indicators Channel status, operating state, module status
Horizontal Yes
Cutoff frequency 5 kHz
Max. gain drift 12 ppm/°C
Conversion time Depends on the configured data output rate
Vertical mounting orientation -25 to 50°C
Data output rate 0.1 - 7500 samples per second, configurable using software (f DATA )
Input protection RC protection
Max. offset drift 2 ppm/°C
Common-mode range 0 to 3 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on inputs "Input +" and "Input -"
CRA (Cyber Resilience Act) In preparation
Horizontal mounting orientation -25 to 60°C
Strain gauge factor 2 to 256 mV/V, configurable using software
Conversion procedure Sigma-delta
Installation elevation above sea level Reduction of ambient temperature by 0.5°C per 100 m
Broken sensor line Value approaching ±end value (status bit "Line monitoring" is set in register "Module status")
ADC filter characteristics Sigma-delta, see section "Filter characteristics of the sigma-delta A/D converter"
Digital converter resolution 24-bit
Valid range of values 0xFF800001 to 0x007FFFFF (-8,388,607 to 8,388,607)
Installation elevation above sea level No limitation
Broken bridge supply line Value approaching 0
Measurement sensor 85 to 5000 Ω
Short-circuit and overload-proof Yes
Insulation voltage between input and bus 500 V eff
Voltage drop for short-circuit protection Max. 0.2 VDC at 65 mA and 25°C
Installation elevation above sea level IP20
Additional power dissipation caused by actuators (resistive) [W] Max. +0.36