Phoenix Contact PSR-SCP- 24UC/ESAM4/3X1/1X2/B fait partie de la gamme PSRclassic en tant que relais de sécurité. Il est spécifié pour les circuits d’arrêt d’urgence. Il se monte sur rail DIN et présente un indice de protection IP20.

Specifications

Brand Phoenix Contact
Model PSR-SCP- 24UC/ESAM4/3X1/1X2/B
Order Number 2900509
Inrush current < 3.5 A (typ. with U S, Δt = 3 ms)
Switching frequency max. 0.5 Hz
Limiting continuous current 6 A
Power consumption at U S typ. 1.68 W
Rated insulation voltage 250 V
Sq. Total current 72 A 2 (observe derating)
Switching voltage min. 10 V AC/DC
Degree of protection IP20
Vibration (operation) 10 Hz ... 150 Hz, 2g
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Ambient temperature (operation) -20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Application Emergency stop
Application Safety door
CO2e kg 5.021 kg CO2e
Color (Housing) yellow (RAL 1018)
Concurrence ∞
Conductor cross-section AWG 24 ... 12
Conductor cross-section flexible 0.2 mm² ... 2.5 mm²
Conductor cross-section rigid 0.2 mm² ... 2.5 mm²
Connection method Screw connection
Contact material AgSnO 2
Contact switching type 3 enabling current paths
Contact switching type 1 signaling current path
Control 2-channel
Current consumption 38 mA (typ. with U S at S12)
Current consumption -38 mA (typ. with U S at S22)
Current consumption 0 mA (typ. with U S at S34)
Current consumption 1 mA (typ. with U S at S35)
Degree of pollution 2
Depth 114.5 mm
Description of the input safety-related
Description of the input non-safety-related
ECLASS-13.0 27371819
ECLASS-15.0 27371819
ECLASS-15.0 ASSET 27250101
Environment friendly use period (EFUP) EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC001449
Exemption 7(a), 7(c)-I
Filter time 5 ms (in the event of voltage dips at U s )
Filter time No test pulses permitted
Fulfills EU RoHS substance requirements Yes
Height 99 mm
Housing material PA
Identification CE-compliant
Input current range "0" signal 0 mA ... 2 mA
Input voltage range "0" signal 0 V DC ... 5 V DC (S12)
Input voltage range "1" signal 20.4 V ... 26.4 V (S12)
Input voltage range "1" signal 20.4 V ... 26.4 V
Inrush current < 100 mA (Δt = 500 ms, with U s /I x at S12)
Inrush current > -100 mA (Δt = 300 ms, with U s /I x at S22)
Inrush current < 6 mA (typ. with U S at S34/35)
Inrush current min. 10 mA
Inrush current max. 6 A
Interrupting rating (ohmic load) max. Observe derating and load limit curve
Limiting continuous current 6 A (Signaling current path)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance 50 Ω
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Maximum altitude ≤ 2000 m (Above sea level)
Maximum power dissipation for nominal condition 16.44 W (U S = 26.4 V, I L ² = 72 A², P Total max = 2.04 W + 14.4 W)
Mechanical service life approx. 10 7 cycles
Mechanical service life 10 7 cycles
Min. degree of protection of inst. location IP54
Minimum order quantity 1 pc
Mounting position vertical or horizontal
Mounting type DIN rail mounting
Nominal operating mode 100% operating factor
Number of inputs 2
Number of outputs 3
Number of outputs 1
Operating voltage display 1 x LED (green)
Output description 2 N/O contacts in series, safety-related, floating
Output description 2 N/C contacts parallel, non-safety-related, floating
Output fuse 10 A gL/gG (High demand)
Output fuse 4 A gL/gG (Low demand)
Output fuse 6 A gL/gG
Overvoltage category III
Packing unit 1 pc
Performance level (PL) e (5 A DC13; 5 A AC15; 8760 switching cycles/year)
Pluggable yes
Product key DNA114
Product type Safety relays
Protective circuit Serial protection against polarity reversal; Suppressor diode
Protective circuit Suppressor diode
Rated control circuit supply voltage U S 24 V DC -15 % / +10 %
Rated control supply current I S typ. 70 mA (at U S )
Rated surge voltage/insulation See data sheet, section “Insulation coordination”.
Recovery time < 1 s (following demand of the safety function)
Relay type Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Restart time < 1 s (Boot time)
Safety Integrity Level (SIL) 3
Scip c5628219-0111-45f5-ad67-02317d0643d9
Screw thread M3
Set comprises 1449149 PSR-SCP- 24UC/ESAM4/3X1/1X2/B-SET10
Shock 15g
Sq. Total current 36 A 2
Start pulse length ≥ 500 ms (manual start)
Status display 3 x LED (green)
Stop category (EN 60204-1) 0
Stripping length 7 mm
Switching capacity 5 A (AC 15)
Switching capacity 6 A (DC 13)
Switching capacity 1.5 A (AC 15)
Switching capacity 2 A (DC 13)
Switching power min. 100 mW
Switching voltage max. 250 V AC/DC
Tightening torque 0.5 Nm ... 0.6 Nm
Typ. starting time with U s typ. 250 ms (with Us / when controlled via A1)
Typical release time typ. 20 ms (At Us on demand via sensor circuit)
Typical release time typ. 45 ms (At Us/on demand via A1)
Typical response time typ. 150 ms (For U s autostart)
Typical response time typ. 100 ms (For U s manual, monitored start)
UNSPSC 21.0 39122205
Weight per piece (excluding packing) 161.1 g
Weight per piece (including packing) 191.91 g
Width 22.5 mm