Saltar al contenido

Phoenix Contact TRIO-PS-2G/3AC/24DC/20 2903155 fuente de alimentación - Usada

Phoenix Contact TRIO-PS-2G/3AC/24DC/20 2903155 fuente de alimentación - Usada

Solicitar cotizacion

Cantidad, estado y destino.

Solicitar cotizacion

Descripcion

Fuente de alimentación Phoenix Contact TRIO-PS-2G/3AC/24DC/20 usada, número de pedido 2903155. Acepta entrada trifásica de 400–500 V AC y proporciona salida de 24 V DC a 20 A, con una potencia máxima de 480 W. La unidad fue retirada de un equipo y muestra un desgaste mínimo.

Especificaciones

Brand Phoenix Contact
Model TRIO-PS-2G/3AC/24DC/20
Order Number 2903155
HS Code 850440
Voltage 10 V (Test Level 3)
Frequency 50 Hz
Output Current 20 A
Continuous load current 100 mA
Inrush current ≤ 22 A (typical)
Nominal output voltage 24 V DC ±1 %
Power factor 0.63
Power loss nominal load max. < 38 W (480 V AC)
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Typical national grid voltage 3x 400 V AC
Voltage type of supply voltage AC
AC frequency range 50 Hz ... 60 Hz
Frequency range Class A, B
Input Frequency 50-60 Hz
Input voltage range 3x 400 V AC ... 500 V AC -20 % ... +15 %
Nominal input voltage range 3x 400 V AC ... 500 V AC
Degree of protection IP20
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Startup Temperature -40°C / -40°F startup (type tested)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation) 15 Hz ... 150 Hz, 4g, 90 min.
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise emission EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EMC requirements for noise immunity EN 61000-6-2
REACH candidate substance (CAS No.) Diboron trioxide (CAS: 1303-86-2)
REACH candidate substance (CAS No.) Lead monoxide (lead oxide) (CAS: 1317-36-8)
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Shipbuilding approval GL applied for
13/14 U OUT > 0.9 x U N (U N = 24 V DC)
Additional text Test Level 2
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
CO2e kg 40.66 kg CO2e
Color green
Comments Criterion A
Comments Criterion B
Conductor cross-section AWG max. 12
Conductor cross-section AWG max. 8
Conductor cross-section AWG max. 16
Conductor cross-section AWG min. 24
Conductor cross-section flexible max. 2.5 mm²
Conductor cross-section flexible max. 6 mm²
Conductor cross-section flexible max. 1.5 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section, rigid max. 4 mm²
Conductor cross-section, rigid max. 10 mm²
Conductor cross-section, rigid max. 1.5 mm²
Conductor cross-section, rigid min. 0.2 mm²
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Connection method Push-in connection
Contact discharge 6 kV (Test Level 4)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Control deviation < 0.1 % (change in input voltage ±10 %)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Current consumption 3x 1.2 A (400 V AC)
Current consumption 3x 1 A (500 V AC)
Current consumption 2x 2.3 A (400 V AC)
Current consumption 2x 1.9 A (500 V AC)
DC OK U OUT > 0.9 x U N (U N = 24 V DC)
Default closed
Degree of pollution 2
Depth 160 mm
Derating > 60 °C ... 70 °C (2.5 %/K)
Digital 30 V AC 30 V DC 100 mA
Discharge current to PE < 3.5 mA
Discharge current to PE < (550 V AC, 60 Hz)
Discharge in air 8 kV (Test Level 4)
Dynamic Boost 30A (5s)
Dynamic Boost (I Dyn.Boost ) 30 A (5 s)
ECLASS-13.0 27040701
ECLASS-15.0 27040701
Efficiency > 91.5 % (400 V AC)
Efficiency typ. 91.8 % (480 V AC)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Environment friendly use period (EFUP) EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC002540
Exemption 7(a), 7(c)-I
Frequency range 0 kHz ... 2 kHz
Frequency range 80 MHz ... 6 GHz
Frequency range 0.15 MHz ... 80 MHz
Fulfills EU RoHS substance requirements Yes
Height 130 mm
Hood version Polycarbonate
Housing material Metal
Input 4 kV (Test Level 4 - asymmetrical)
Input 3 kV (Test Level 3 - symmetrical)
Input 6 kV (Test Level 4 - asymmetrical)
Input Current 2ac 2 x 2.3-1.9 A
Input Current 3ac 3 x 1.2-1.0 A
Input fuse 3.15 A (internal (device protection), slow-blow)
Input Voltage 2ac 2 x 400-500 V~ (-10% / +15%)
Input Voltage 3ac 3 x 400-500 V~ (-20% / +15%)
Input voltage range 2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range AC 3x 320 V AC ... 575 V AC
Input/Output asymmetrical
Inrush current integral (I 2 t) ≤ 0.5 A 2 s
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Insulation voltage input/output 3 kV AC (type test)
Insulation voltage input/output 1.5 kV AC (routine test)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Mains buffering time typ. 10 ms (400 V AC)
Mains buffering time typ. 20 ms (500 V AC)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Maximum altitude ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Maximum no-load power dissipation < 1.2 W (400 V AC)
Minimum order quantity 1 pc
Mounting position horizontal DIN rail NS 35, EN 60715
Mounting type DIN rail mounting
MTBF (IEC 61709, SN 29500) > 1800000 h (25 °C)
MTBF (IEC 61709, SN 29500) > 1100000 h (40 °C)
MTBF (IEC 61709, SN 29500) > 510000 h (60 °C)
Network type Star network
No-load proof yes
Nominal input voltage range 2x 400 V AC ... 500 V AC
Nominal output current (I N ) 20 A
Nominal power consumption 822.2 VA
Number of periods 25 periods
Number of periods 10 periods
Number of periods 1 period
Number of phases 3
Output 2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
Output 2 kV (Test Level 1 - asymmetrical)
Output characteristic U/I with dynamic load reserve
Output power 480 W
Output power 720 W (5 s)
output_voltage 24 V=
Overvoltage category (EN 62368-1) II (≤ 2000 m)
Packing unit 1 pc
Product key CMPO33
Product type Power supply
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Protection class I (in closed control cabinet)
Protective circuit Transient surge protection; Varistor
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Rail applications EN 50121-4
Residual ripple ≤ 50 mV PP
Rise time ≤ 120 ms (U OUT (10 % ... 90 %))
Scip 77f69704-4d41-4759-b065-1fc3ee8e18d6
Setting range of the output voltage (U Set ) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Short-circuit-proof yes
Signal 1 kV (Test Level 2 - asymmetrical)
Signal 1 kV (Test Level 1 - asymmetrical)
Signalization designation DC OK
SIL in accordance with IEC 61508 0
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, max. 6 mm²
Single conductor/terminal point, stranded, with ferrule, max. 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Standard - Electrical safety IEC 62368-1 (SELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standards/regulations EN 55016
Standards/regulations EN 61000-6-3 (Class B)
Standards/regulations EN 55011 (EN 55022)
Standards/regulations EN 61000-4-2
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Standards/regulations EN 61000-4-5
Standards/regulations EN 61000-4-6
Standards/regulations EN 61000-4-11
Standards/regulations EN 61000-6-3
Status display LED
Stripping length 10 mm
Stripping length 15 mm
Stripping length 8 mm
terminal blocks) V0
Test field strength 10 V/m (Test Level 3)
Type of housing Aluminum (AlMg3)
Types of signaling LED
Types of signaling Floating signal contact
Typical national grid voltage 3x 480 V AC
Typical response time < 1 s
UL approvals UL Listed UL 508
UL approvals UL/C-UL Recognized UL 60950-1
UNSPSC 21.0 39121000
Voltage 230 V AC
Voltage Adjustment 24-28 V
Voltage dip 70 %
Voltage dip 40 %
Voltage dip 0 %
Weight per piece (excluding packing) 1,493.96 g
Weight per piece (including packing) 1,706 g
Width 65 mm
With protective coating no