Saltar al contenido

Fuente de alimentación Phoenix Contact QUINT4-PS/1AC/24DC/40

Fuente de alimentación Phoenix Contact QUINT4-PS/1AC/24DC/40

Solicitar cotizacion

Cantidad, estado y destino.

Solicitar cotizacion

Descripcion

Phoenix Contact QUINT4-PS/1AC/24DC/40 suministra una salida de 24 V DC a 40 A y se monta en carril DIN de 35 mm.

Especificaciones

Brand Phoenix Contact
Model QUINT4-PS/1AC/24DC/40
Order Number 2904603
HS Code 850440
Voltage 10 V (Test Level 3)
Frequency 16.7 Hz
Current 20 A
Inrush current typ. 12 A (at 25 °C)
Nominal output voltage 24 V DC
Power dissipation SLEEP MODE < 3 W (120 V AC)
Power dissipation SLEEP MODE < 3 W (230 V AC)
Power loss nominal load max. < 50 W (120 V AC)
Power loss nominal load max. < 50 W (230 V AC)
Standard – Safety extra-low voltage IEC 61010-1 (SELV)
Typical national grid voltage 120 V AC
Voltage type of supply voltage AC
Switching frequency 85.00 kHz ... 107.00 kHz (Auxiliary converter stage)
Frequency range 0 kHz ... 2 kHz
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Nominal input voltage range 100 V AC ... 240 V AC
Degree of protection IP20
Recommended breaker for input protection 16 A ... 20 A (Characteristic B, C, D, K or comparable)
Vibration (operation) 5 Hz ... 100 Hz resonance search 0.7g, 90 min., resonance frequency 0.7g, 90 min. (in accordance with DNV GL Class A)
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise emission EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EMC requirements for noise immunity EN 61000-6-2
EMC requirements for power supply IEC 61850-3 (G,H)
EMC requirements for power supply EN 61000-6-5 (switching devices)
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Shipbuilding approval DNV GL
Additional text 120 V AC
Additional text 230 V AC
Additional text Area power distribution
Additional text Bridge and deck area
Additional text 60 s
Additional text 3 s
Additional text DC, 60 s
Additional text Test Level 2
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Approval - requirement of the semiconductor industry with regard to mains voltage dips SEMI F47-0706, EN 61000-4-11
Battery charging DIN 41773-1
Climatic class 3K3 (in acc. with EN 60721)
CO2e kg 63.176 kg CO2e
Comments Criterion A
Comments Criterion A: 0.5 / 1 / 25 / 30 periods
Comments Criterion A: 0.5 / 1 period Criterion B: 5 / 50 / 250 periods
Conductor cross-section AWG max. 10
Conductor cross-section AWG max. 6
Conductor cross-section AWG max. 16
Conductor cross-section AWG min. 24
Conductor cross-section AWG min. 20
Conductor cross-section flexible max. 4 mm²
Conductor cross-section flexible max. 16 mm²
Conductor cross-section flexible max. 1.5 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section flexible min. 0.5 mm²
Conductor cross-section, rigid max. 6 mm²
Conductor cross-section, rigid max. 16 mm²
Conductor cross-section, rigid max. 1 mm²
Conductor cross-section, rigid min. 0.2 mm²
Conductor cross-section, rigid min. 0.5 mm²
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Connection method Screw connection
Connection method Push-in connection
Contact discharge 8 kV (Test Level 4)
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
Control deviation < 1 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Control deviation < 0.25 % (change in input voltage ±10 %)
Control input (configurable) Rem Output power ON/OFF (SLEEP MODE)
Crest factor typ. 1.5 (120 V AC)
Crest factor typ. 1.6 (230 V AC)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Csa CAN/CSA-C22.2 No. 60950-1-07
CSA CSA-C22.2 No. 107.1-01
Current 40 A
Current consumption 13.6 A (100 V AC)
Current consumption 10 A (120 V AC)
Current consumption 5.2 A (230 V AC)
Current consumption 5.4 A (240 V AC)
Current consumption 12 A (110 V DC)
Current consumption 5 A (250 V DC)
Default Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
Default 24 V DC 20 mA 24 V DC for U Out > 0.9 x U Set
Default 24 V DC 20 mA 24 V DC for P Out < P N
Default closed (U out > 0.9 U Set )
Degree of pollution 2
Depth 140 mm
Derating > 60 °C ... 70 °C (2.5 %/K)
Digital 24 V DC 20 mA
Digital 24 V DC 1 A
Digital 30 V AC/DC 0.5 A
Discharge current to PE < 3.5 mA
Discharge current to PE 1.7 mA (264 V AC, 60 Hz)
Discharge in air 15 kV (Test Level 4)
Dnv Class A
DNV Class B
Dynamic Boost (I Dyn.Boost ) 60 A (5 s)
ECLASS-13.0 27040701
ECLASS-15.0 27040701
Efficiency typ. 94.8 % (120 V AC)
Efficiency typ. 95.9 % (230 V AC)
Electric strength, max. 300 V AC 60 s
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Environment friendly use period (EFUP) EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
Environmental protection directive RoHS Directive 2011/65/EU
Environmental protection directive WEEE
Environmental protection directive Reach
ETIM 10.0 EC002540
Exemption 7(a), 7(c)-I
Feedback voltage resistance ≤ 35 V DC
Frequency 50 Hz
Frequency 60 Hz
Frequency 0 Hz
Frequency range 80 MHz ... 1 GHz
Frequency range 1 GHz ... 6 GHz
Frequency range 0.15 MHz ... 80 MHz
Frequency range 50 Hz ... 60 Hz
Frequency range (f N ) 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (f N ) 16.7 Hz (acc. to EN 50163)
Fulfills EU RoHS substance requirements Yes
Fuse protection (secondary side) electronic
Fuse protection (secondary side) thermal-magnetic
Fuse protection (secondary side) thermal
HART FSK Physical Layer Test Specification Compliance Output voltage U Out compliant
Height 130 mm
Hood version Stainless steel X6Cr17
Housing material Metal
Input 4 kV (Test Level 4 - asymmetrical)
Input typ. 3 kV (Test Level 4 - symmetrical)
Input typ. 6 kV (Test Level 4 - asymmetrical)
Input 2 kV (Test Level 4 - symmetrical)
Input fuse 16 A (slow-blow, internal)
Input voltage range 110 V DC ... 250 V DC -18 % ... +40 %
Input, output (test level 1) 100 kHz 1 MHz (Test Level 3 - symmetrical)
Input, output (test level 2) 10 MHz
Input, output (test level 3) 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Input/output/signal asymmetrical
Inrush current integral (I 2 t) < 1 A 2 s
Inrush current limitation 12 A (after 1 ms)
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Insulation voltage input/output 4 kV AC (type test)
Insulation voltage input/output 2 kV AC (routine test)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Magnetic circuit breaker tripping A1...A40 / B2...B25 / C1...C13 / Z1...Z16
Mains buffering time typ. 29 ms (120 V AC)
Mains buffering time typ. 32 ms (230 V AC)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Maximum no-load power dissipation < 4 W (120 V AC)
Maximum no-load power dissipation < 4 W (230 V AC)
Minimum order quantity 1 pc
Mounting position horizontal DIN rail NS 35, EN 60715
Mounting type DIN rail: 35 mm
MTBF (IEC 61709, SN 29500) > 934000 h (25 °C)
MTBF (IEC 61709, SN 29500) > 555000 h (40 °C)
MTBF (IEC 61709, SN 29500) > 249000 h (60 °C)
Network type Star network
No-load proof yes
Nominal input voltage range 110 V DC ... 250 V DC
Nominal output current (I N ) 40 A
Nominal power consumption 1064 VA
Number of periods 0.5 / 1 / 25 / 30 periods
Number of periods 5 / 10 / 50 periods
Number of periods 0,5 / 1 / 5 / 50 / 250 periods
Number of phases 1
Output 4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Output power 960 W
Output power 1080 W
Output power 1440 W
Overvoltage category (EN 61010-1) II (≤ 5000 m)
Overvoltage category (EN 62477-1) III (≤ 2000 m)
P Out > 100 % (LED lights up yellow, output power > 960 W)
P Out > 75 % (LED lights up green, output power > 720 W)
P Out > 50 % (LED lights up green, output power > 480 W)
Packing unit 1 pc
PE 2.5 kV AC (type test)
PE 0.5 kV DC (type test)
PE 2.4 kV AC (routine test)
PE 0.5 kV DC (routine test)
Product key CMPI13
Product type Power supply
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Protection class I
Rail applications EN 50121-3-2
Rail applications EN 50121-4
Rail applications EN 50121-5
Rail applications EN 50163
Rail applications IEC 62236-3-2
Rail applications IEC 62236-4
Rail applications IEC 62236-5
Residual ripple < 50 mV PP (with nominal values)
Scip 4654ca05-2cdc-49da-8da0-92691aa78cca
Selective Fuse Breaking (I SFB ) 215 A (15 ms)
Setting range of the output voltage (U Set ) 24 V DC ... 29.5 V DC (constant capacity)
Shock 11 ms, 15 g, in each space direction (according to IEC 60068-2-27)
Short-circuit-proof yes
Side element version Aluminum
Signal 4 kV (Test Level 4 - asymmetrical)
Signal ground SGnd Reference potential for Out1, Out2, and Rem
Signal option Output current
Signal option Output voltage
Signal option Output power
Signal option U IN input voltage OK
Signal option Operating hours
Signal option Early warning of high temperatures
Signal option OVP voltage limitation active
Signals (test level 1) 100 kHz 1 MHz (Test Level 3 - symmetrical)
Signals (test level 2) 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 16 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 0.75 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 16 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 1.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.2 mm²
Siq BG (type approved)
Standard - Electrical safety IEC 61010-2-201 (SELV)
Standard - Safe isolation IEC 61558-2-16
Standard - Safe isolation IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1
Standard - Safety of transformers EN 61558-2-16
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Safety extra-low voltage IEC 61010-2-201 (PELV)
Standards/regulations EN 55016
Standards/regulations EN 61000-6-3 (Class B)
Standards/regulations Additional basic standard EN 61000-6-5 (immunity in switching devices), IEC/EN 61850-3 (power supply)
Standards/regulations EN 61000-3-2
Standards/regulations EN 61000-3-2 (Class A)
Standards/regulations EN 61000-3-3
Standards/regulations EN 61000-4-2
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Standards/regulations EN 61000-4-5
Standards/regulations EN 61000-4-6
Standards/regulations EN 61000-4-8
Standards/regulations EN 61000-4-11
Standards/regulations EN 61000-4-9
Standards/regulations EN 61000-4-12
Standards/regulations EN 61000-4-16
Standards/regulations EN 61000-4-18
Standards/regulations EN 61000-4-10
Static Boost (I Stat.Boost ) 45 A
Stripping length 8 mm
Stripping length 10 mm
Switching frequency 45.00 kHz ... 200.00 kHz (Main converter stage)
Switching frequency 50.00 kHz ... 500.00 kHz (PFC stage)
Temperature 40 °C
Temperature 25 °C
Temperature code T4 (-25 ... +70 °C; > 60 °C, Derating: 2,5 %/K)
terminal blocks) V0
Test field strength 20 V/m (Test Level 3)
Test field strength 10 V/m (Test Level 3)
Test field strength 100 A/m
Test field strength 1 kA/m
Test field strength 300 A/m
Test field strength 1000 A/m
Test field strength 110 A/m
Test level 1 15 Hz 150 Hz (Test Level 4)
Test level 1 100 kHz
Test level 2 150 Hz 1.5 kHz (Test Level 4)
Test level 2 1 MHz
Test level 3 1.5 kHz 15 kHz (Test Level 4)
Test level 4 15 kHz 150 kHz (Test Level 4)
Test level 5 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Test level 6 150 Hz 180 Hz (Test Level 4)
Test level 7 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Tightening torque max 0.6 Nm
Tightening torque max 1.5 Nm
Tightening torque, min 0.5 Nm
Tightening torque, min 1.2 Nm
Time 394000 h
Time 452000 h
Time 320000 h
Time 422000 h
Time 113000 h
Time 149000 h
Types of signaling LED
Types of signaling Floating signal contact
Types of signaling Active signal output Out1 (digital, configurable)
Types of signaling Active signal output Out2 (analog, configurable)
Types of signaling Remote contact
Types of signaling Signal ground SGnd
Typical national grid voltage 230 V AC
U Out > 0.9 x U Set (LED lights up green)
U Out < 0.9 x U Set (LED flashes green)
UL approvals UL Listed UL 508
UL approvals UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UNSPSC 21.0 39121000
Voltage 230 V AC
Voltage 30 V 3 V
Voltage 3 V
Voltage 3 V 30 V
Voltage 30 V
Voltage 30 V (Permanent)
Voltage 300 V (1 s)
Voltage 1 kV
Voltage 2.5 kV
Voltage dip 70 %
Voltage dip 40 %
Voltage dip 0 %
Voltage type of supply voltage DC
Weight per piece (excluding packing) 2,887 g
Weight per piece (including packing) 3,250 g
Width 120 mm
With protective coating no