Zum Inhalt springen

Phoenix Contact ELR H51-IESSC-24DC500AC-9 Hybrid-Motorstarter

Phoenix Contact ELR H51-IESSC-24DC500AC-9 Hybrid-Motorstarter

Angebot anfragen

Menge, Zustand und Zielort angeben.

Angebot anfragen

Beschreibung

Phoenix Contact ELR H51-IESSC-24DC500AC-9 Hybrid-Motorstarter zur Montage auf einer Stromschiene mit Schraubanschlüssen.

Spezifikationen

Brand Phoenix Contact
Model ELR H51-IESSC-24DC500AC-9
Order Number 2902745
Leakage current 0 mA
Response time < 2 s
Rated insulation voltage 500 V
Rated surge voltage 6 kV
Switching frequency ≤ 2 Hz (Load-dependent)
Control supply voltage range 19.2 V DC ... 30 V DC
Load current range 1.5 A ... 9 A (see to derating)
Mains frequency 50/60 Hz
Operating voltage range 42 V AC ... 550 V AC
Triggering voltage range 19.2 V DC ... 30 V DC
Degree of protection IP20
REACH candidate substance (CAS No.) 1-Methyl-2-pyrrolidone (NMP) (CAS: 872-50-4)
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Altitude ≤ 2000 m
Ambient temperature (operation) -25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Category code NLDX / NRNT
Certificate PTB 12 ATEX 3004
Certificate NLDX.E228652
Certificate 2020970304000811
Conductor cross-section AWG 24 ... 14
Conductor cross-section flexible 0.2 mm² ... 2.5 mm²
Conductor cross-section rigid 0.2 mm² ... 2.5 mm²
Connection method Screw connection
Contact switching type 1 changeover contact
Cooling time 20 min (for auto reset)
Coordination type 2
Degree of pollution 2
Depth 114.5 mm
ECLASS-13.0 27370905
ECLASS-15.0 27370905
ECLASS-15.0 ASSET 27250101
Environment friendly use period (EFUP) EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
Error indication Red LED
ETIM 10.0 EC001037
Exemption 7(a), 7(c)-I
Fla 6.5 A (500 V AC)
Flammability rating according to UL 94 (Housing) V0 (Housing)
Fulfills EU RoHS substance requirements Yes
Group installation 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Group installation 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Height 160 mm
Identification  II (2) G [Ex e] [Ex d] [Ex px]
Identification  II (2) D [Ex t] [Ex p]
Identification ≤ 3
Identification 2
Identification e
Identification GB/T 14048.6-2016
Input name Control input right/left
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuit Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuit Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Maximum power dissipation 12 W
Maximum power dissipation for nominal condition 11 W
Minimum order quantity 1 pc
Minimum power dissipation 0.88 W
Motor starter type Reversing starter
Mounting position vertical (horizontal DIN rail, motor output below)
Mounting type Bus bar mounting
Mounting type DIN rail mounting
Number of phases 3
Operate threshold > 45 A
Operating mode 100% operating factor
Operating voltage display Green LED
Overvoltage category III
Packing unit 1 pc
Product key DK7454
Product type Hybrid motor starters
Protective circuit Surge protection
Protective circuit Reverse polarity protection; Parallel polarity protection diode
Protective circuit Reverse polarity protection
Protective circuit Surge protection; Varistor
Protective circuit Short-circuit protection; Fuse
Rated actuating current I C 5 mA
Rated actuating voltage U C 24 V DC
Rated control circuit supply voltage U S 24 V DC
Rated control supply current I S 40 mA
Rated operating voltage U e 500 V AC
Sccr 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
SCCR 5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
Scip 3bb8249d-06af-482f-a35b-ffe197ab31a3
Screw thread M3
Standards/regulations IEC 60947-1
Standards/regulations EN 60947-4-2
Standards/regulations IEC 61508
Standards/regulations ISO 13849
Status display LED (yellow)
Stripping length 8 mm
Switching capacity in accordance with IEC 60947-5-1 3 A (230 V, AC 15)
Switching capacity in accordance with IEC 60947-5-1 2 A (24 V (DC 13))
Switching level < 5 V DC (For EMERGENCY STOP)
Switching threshold 9.6 V (“0” signal)
Switching threshold 19.2 V (“1” signal)
Tightening torque 0.5 Nm ... 0.6 Nm
Tightening torque 5 lb f -in. ... 7 lb f -in.
Trigger characteristic in acc. with IEC 60947-4-2 Class 10A
Typical turn-off time < 30 ms
UNSPSC 21.0 25173900
Weight per piece (excluding packing) 350 g
Weight per piece (including packing) 432.45 g
Width 22.5 mm