Especificacoes
| Brand | Keyence |
|---|---|
| Model | KV-NC32EX |
| Maximum input voltage | 26.4 VDC |
| Weight | Approx. 110 g |
| Common method | 32 points/1 common (2 terminals) *1 |
| External connection method | Connector |
| Input impedance | 4.4 kΩ |
| Input Points | 32 points |
| Input rated voltage | 1 mA |
| Input rated voltage | 5.2 mA |
| Input terminals | 24 VDC mode, 5 VDC mode |
| Internal current consumption | ≤20 mA |
| Maximum OFF current | 1.5 mA |
| Maximum OFF voltage | 1.5 V |
| Minimum ON voltage | 3.5 V |
| Minimum ON voltage | 19 V |
| OFF to ON: Max. | 25 μs : 50 μs 300 μs : 290 μs 1 ms : 1.2 ms 10ms : 11 ms |
| OFF to ON: Typ. | 25 μs : 10 μs 300 μs : 240 μs 1 ms : 1 ms 10ms : 10 ms |
| ON to OFF: Max. | 25 μs : 150 μs 300 μs : 390 μs 1 ms : 1.2 ms 10 ms : 11 ms |
| ON to OFF: Typ. | 25 μs : 50 μs 300 μs : 280 μs 1 ms : 1 ms 10ms : 10 ms |