Skip to content

WAGO 753-425 I/O Module - Digital Input

WAGO 753-425 I/O Module - Digital Input

Request a Quote

Quantity, condition and destination.

Request quote

Description

WAGO 753-425 I/O module provides 2 digital input channels.

Specifications

Brand WAGO
MPN 753-425
Connection type Input
Open-circuit voltage 8.2 V
Short-circuit current ≤ 8.2 mA
Weight 42.4 g
Vibration resistance 4g per IEC 60068-2-6
CAS-No. 1303-86-2; 1317-36-8; 25550-51-0; 7439-92-1
EMC emission of interference per EN 61000-6-4, marine applications
EMC immunity to interference per EN 61000-6-2, marine applications
REACH Candidate List Substance 4-Methyl-1,2-cyclohexanedicarboxylic anhydride; Diboron trioxide; Lead; Lead monoxide
Ambient temperature (operation) 0 … +55 °C
Ambient temperature (storage) -40 … +85 °C
Color light gray
Conformity marking CE
Connectable conductor materials Copper
Connection technology 8 x CAGE CLAMP® (inputs)
Current carrying capacity (power jumper contacts) 10 A
Current consumption (system supply) 5 mA
Data width 4-bit input: 2-bit data, 2-bit error (short circuit/wire break)
Depth 69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail 62.6 mm / 2.465 inches
Diagnostics Short circuit, wire break
Eccn NO US CLASSIFICATION
eCl@ss 10.0 27-24-26-04
eCl@ss 9.0 27-24-26-04
ETIM 10.0 EC001599
ETIM 9.0 EC001599
Exposure to pollutants per IEC 60068-2-42 and IEC 60068-2-43
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Fire load 1.013 MJ
Height 100 mm / 3.937 inches
Housing material Polycarbonate; polyamide 6.6
Indicators LED (A, C) green: Status DI 1, DI 2; LED (B, D) red: Error DI 1, DI 2
Input characteristic high-side switching
Input data width (internal) max. 4 Bit
Input filter 3 ms
Input pulse separation ≥3 ms
Input resistance 1,000 Ω
Isolation 500 V system/field
Mounting position Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Mounting type DIN-35 rail
Number of digital inputs 2
Number of incoming power jumper contacts 2
Number of outgoing power jumper contacts 2
Operating altitude 0 … 2000 m / 0 … 6562 ft
Permissible H2S contaminant concentration at a relative humidity < 75 % 10 ppm
Permissible SO2 contaminant concentration at a relative humidity < 75 % 25 ppm
Pluggable connector pluggable
Pollution degree 2 per IEC 61131-2
Protection against incorrect wiring Short circuit monitoring: > 6.5 mA; Wire break monitoring: < 0.2 mA
Protection type IP20
PU (SPU) 1 pcs
Relative humidity (without condensation) 95 %
RoHS Compliance Status Compliant,With Exemption
SCIP notification number (Bulgaria) 43217679-07b3-407a-9c53-ea23b0bee863
SCIP notification number (Czech Republic) 916efe91-d573-46e0-bbdd-c550b75850f4
Sensor connection 2 x (2-wire)
Sensor supply 8.2 VDC
Shock resistance 15g per IEC 60068-2-27
Signal current (0) NAMUR ≤1.2 mA
Signal current (1) NAMUR ≥2.1 mA
Signal type NAMUR
Solid conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Strip length 9 … 10 mm / 0.35 … 0.39 inches
Supply voltage (field) 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Supply voltage (system) 5 VDC; via data contacts
Switching hysteresis 0.2 mA
Total number of channels (module) 2
Unspsc 32,151,705
Width 12 mm / 0.472 inches