Skip to content

Phoenix Contact PSR-SCP-24UC/ESA2/4X1/1X2/B 2963802 safety relay - Used

Phoenix Contact PSR-SCP-24UC/ESA2/4X1/1X2/B 2963802 safety relay - Used

Request a Quote

Quantity, condition and destination.

Request quote

Description

Used Phoenix Contact PSR-SCP-24UC/ESA2/4X1/1X2/B 2963802 safety relay.

Specifications

Brand Phoenix Contact
Model PSR-SCP-24UC/ESA2/4X1/1X2/B
Order Number 2963802
Input Voltage 24 VAC/DC -15/+10%
Switching frequency max. 0.5 Hz
Inrush current < 3.5 A (typ. with U S, Δt = 2 ms)
Limiting continuous current 6 A
Power consumption at U S typ. 1.32 W
Rated insulation voltage 250 V AC
Sq. Total current 72 A 2 (observe derating)
Switching voltage min. 10 V
Degree of protection IP20
Vibration (operation) 10 Hz ... 150 Hz, 2g
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Ambient temperature (operation) -20 °C ... 65 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Application Emergency stop
Application Safety door
CO2e kg 4.417 kg CO2e
Color (Housing) yellow (RAL 1018)
Conductor cross-section AWG 24 ... 12
Conductor cross-section flexible 0.2 mm² ... 2.5 mm²
Conductor cross-section rigid 0.2 mm² ... 2.5 mm²
Connection method Screw connection
Contact material AgSnO 2
Contact switching type 4 enabling current paths
Contact switching type 1 signaling current path
Control 1-channel
Current consumption typ. 50 mA (with U S at S11)
Current consumption typ. 52 mA (with U S supplied externally)
Current consumption 0 mA (typ. with U S )
Degree of pollution 2
Depth 114.5 mm
Description of the input safety-related
Description of the input non-safety-related
ECLASS-13.0 27371819
ECLASS-15.0 27371819
ECLASS-15.0 ASSET 27250101
Environment friendly use period (EFUP) EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC001449
Exemption 7(a), 7(c)-I
Filter time 2 ms (in the event of voltage dips at U s )
Filter time No brightness test pulses / high test pulses permitted.
Filter time 1 ms (Test pulse width of low test pulses)
Filter time 1 s (Test pulse rate for low test pulse)
Filter time No test pulses permitted
Fulfills EU RoHS substance requirements Yes
Height 99 mm
Housing material PA
Identification CE-compliant
Input current range "0" signal 0 mA ... 2 mA
Input voltage range "0" signal 0 V DC ... 5 V DC
Input voltage range "1" signal 20.4 V ... 26.4 V
Inrush current 80 mA (typ. with U S, Δt = 150 ms)
Inrush current < 6 mA (typ. with U S, Δt = 65 ms)
Inrush current min. 10 mA
Inrush current max. 20 A (Δt = 100 ms)
Inrush current max. 6 A
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance 50 Ω
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Maximum altitude ≤ 2000 m (Above sea level)
Maximum power dissipation for nominal condition 16 W (U S = 26.4 V, I L ² = 72 A²,P Total max = 1.6 W + 14.4 W)
Mechanical service life 10x 10 6 cycles
Mechanical service life 10 7 cycles
Min. degree of protection of inst. location IP54
Minimum order quantity 1 pc
Mounting position vertical or horizontal
Mounting type DIN rail mounting
Nominal operating mode 100% operating factor
Number of inputs 1
Number of outputs 4
Number of outputs 1
Operating voltage display 1 x LED (green)
Output Current Ac15 4 A
Output Current Dc13 4 A
Output description 2 N/O contacts in series, safety-related, floating
Output description 2 N/C contacts parallel, non-safety-related, floating
Output fuse 10 A gL/gG (High demand)
Output fuse 4 A gL/gG (Low demand)
Output fuse 6 A gL/gG
Output Voltage AC 250 V AC
Overvoltage category III
Packing unit 1 pc
Performance level (PL) e (3 A DC13; 3 A AC15; 8760 switching cycles/year)
Performance level (PL) e (5 A DC13; 3 A AC15; 4380 switching cycles/year)
Pluggable yes
Product key DNA111
Product type Safety relays
Protective circuit Serial protection against polarity reversal; Suppressor diode
Protective circuit Suppressor diode
Rated control circuit supply voltage U S 24 V DC -15 % / +10 %
Rated control supply current I S typ. 55 mA (at U S )
Rated surge voltage/insulation Basic insulation 4 kV: between all current paths and housing Safe isolation, reinforced insulation 6 kV: between A1/A2 and 13/14, 23/24, 33/34, 43/44 between S11/S12/S33/S34 and 13/14, 23/24, 33/34, 43/44 between 51/52 and 13/14, 23/24, 33/34, 43/44
Recovery time < 1 s (following demand of the safety function)
Relay type Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Restart time < 1 s (Boot time)
Safety Integrity Level (SIL) 3
Scip 0cde4f44-4521-4b22-8d20-64858a0ac0dc
Screw thread M3
Shock 15g
Sq. Total current 36 A 2 (observe derating)
Start pulse length ≥ 500 ms (manual start)
Status display 2 x LED (green)
Stop category (EN 60204-1) 0
Stripping length 7 mm
Switching capacity 3 A (AC 15)
Switching capacity 5 A (DC 13)
Switching capacity 1.5 A (AC 15)
Switching power min. 100 mW
Switching power min. 50 mW
Switching voltage max. 250 V AC/DC
Switching voltage min. 5 V
Tightening torque 0.5 Nm ... 0.6 Nm
Typ. starting time with U s < 100 ms (with Us / when controlled via A1)
Typical release time < 10 ms (At Us on demand via sensor circuit)
Typical release time < 100 ms (At Us/on demand via A1)
Typical response time < 100 ms (For U s autostart)
Typical response time < 100 ms (with U s manual start)
UNSPSC 21.0 39122200
Weight per piece (excluding packing) 127.27 g
Weight per piece (including packing) 200.2 g
Width 22.5 mm