仕様

Brand B&R
Model X20 AI 1744
MPN X20 AI 1744
Origin Austria
Voltage 5.5 VDC / Max. 65 mA
Common-mode range 0 to 3 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on inputs "Input +" and "Input -"
Cutoff frequency 5 kHz
Input protection RC protection
Voltage drop for short-circuit protection Max. 0.2 VDC at 65 mA and 25°C
ADC filter characteristics Sigma-delta, see section "Filter characteristics of the sigma-delta A/D converter"
Additional power dissipation caused by actuators (resistive) [W] Max. +0.36
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
B&R ID code 0x1CDE
Broken bridge supply line Value approaching 0
Broken sensor line Value approaching ±end value (status bit "Line monitoring" is set in register "Module status")
Bus 0.01 W
CE Yes
Connection 4- or 6-wire connections
Conversion procedure Sigma-delta
Conversion time Depends on the configured data output rate
CRA (Cyber Resilience Act) In preparation
Data output rate 0.1 - 7500 samples per second, configurable using software (f DATA )
Digital converter resolution 24-bit
Electrical isolation Bus isolated from analog input and strain gauge supply voltage Channel not isolated from I/O power supply
Full-bridge strain gauge 336 nV
Full-bridge strain gauge 671 nV
Full-bridge strain gauge 1.343 µV
Full-bridge strain gauge 1.31 nV
Full-bridge strain gauge 2.62 nV
Full-bridge strain gauge 5.25 nV
Full-bridge strain gauge 2.686 µV
Full-bridge strain gauge 5.371 μV
Full-bridge strain gauge 10.74 μV
Full-bridge strain gauge 10.49 nV
Full-bridge strain gauge 20.98 nV
Full-bridge strain gauge 41.96 nV
Full-bridge strain gauge 21.48 μV
Full-bridge strain gauge 42.97 μV
Full-bridge strain gauge 83.92 nV
Full-bridge strain gauge 167.85 nV
HazLoc cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Horizontal Yes
Horizontal mounting orientation -25 to 60°C
Input Yes, using LED status indicator and software
Input type Differential, used to evaluate a full-bridge strain gauge
Installation elevation above sea level Reduction of ambient temperature by 0.5°C per 100 m
Installation elevation above sea level No limitation
Installation elevation above sea level IP20
Insulation voltage between input and bus 500 V eff
Internal I/O 0.5 W
KC Yes
Max. gain drift 12 ppm/°C
Max. offset drift 2 ppm/°C
Measurement sensor 85 to 5000 Ω
Module run/error Yes, using LED status indicator and software
Open circuit Yes, using LED status indicator and software
Operation 5 to 95%, non-condensing
Order 3
Pitch 12.5 +0.2 mm
Short-circuit and overload-proof Yes
Slope 60 dB
Status indicators Channel status, operating state, module status
Storage -40 to 85°C
Storage 5 to 95%, non-condensing
Strain gauge factor 2 to 256 mV/V, configurable using software
Transport -40 to 85°C
Transport 5 to 95%, non-condensing
UKCA Yes
UL cULus E115267 Industrial control equipment
Valid range of values 0xFF800001 to 0x007FFFFF (-8,388,607 to 8,388,607)
Vertical Yes
Vertical mounting orientation -25 to 50°C