Phoenix Contact TRIO-PS-2G/3AC/24DC/5 fait partie de la gamme TRIO POWER en tant que alimentation électrique. Il se monte sur rail DIN et présente un indice de protection IP20.

Specifications

Brand Phoenix Contact
Model TRIO-PS-2G/3AC/24DC/5
Order Number 2903153
HS Code 850440
Voltage 10 V (Test Level 3)
AC frequency range 50 Hz ... 60 Hz
Continuous load current 100 mA
Inrush current ≤ 22 A (typical)
Nominal output voltage 24 V DC ±1 %
Power factor 0.55
Power loss nominal load max. < 12 W (480 V AC)
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Typical national grid voltage 3x 400 V AC
Voltage type of supply voltage AC
Frequency range 80 MHz ... 1 GHz
Input voltage range 3x 400 V AC ... 500 V AC -20 % ... +15 %
Nominal input voltage range 3x 400 V AC ... 500 V AC
Degree of protection IP20
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation) 15 Hz ... 150 Hz, 4g, 90 min.
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise emission EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EMC requirements for noise immunity EN 61000-6-2
REACH candidate substance (CAS No.) Diboron trioxide (CAS: 1303-86-2)
REACH candidate substance (CAS No.) Lead monoxide (lead oxide) (CAS: 1317-36-8)
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
13/14 U OUT > 0.9 x U N (U N = 24 V DC)
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
CO2e kg 28.38 kg CO2e
Color green
Comments Criterion A
Comments Criterion B
Conductor cross-section AWG max. 12
Conductor cross-section AWG max. 16
Conductor cross-section AWG min. 24
Conductor cross-section flexible max. 2.5 mm²
Conductor cross-section flexible max. 1.5 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section, rigid max. 4 mm²
Conductor cross-section, rigid max. 1.5 mm²
Conductor cross-section, rigid min. 0.2 mm²
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Connection method Push-in connection
Contact discharge 6 kV (Test Level 4)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Control deviation < 0.1 % (change in input voltage ±10 %)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Current consumption 3x 0.4 A (400 V AC)
Current consumption 3x 0.3 A (500 V AC)
Current consumption 2x 0.6 A (400 V AC)
Current consumption 2x 0.5 A (500 V AC)
DC OK U OUT > 0.9 x U N (U N = 24 V DC)
Default closed
Degree of pollution 2
Depth 115 mm
Derating > 60 °C ... 70 °C (2.5 %/K)
Digital 30 V AC 30 V DC 100 mA
Discharge current to PE < 0.25 mA
Discharge current to PE < (550 V AC, 60 Hz)
Discharge in air 8 kV (Test Level 4)
Dynamic Boost (I Dyn.Boost ) 7.5 A (5 s)
ECLASS-13.0 27040701
ECLASS-15.0 27040701
Efficiency > 91.1 % (at 400 V AC and nominal values)
Efficiency typ. 90.9 % (480 V AC)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Environment friendly use period (EFUP) EFUP-25 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC002540
Exemption 7(a), 7(c)-I
Frequency range 1 GHz ... 2 GHz
Frequency range 2 GHz ... 3 GHz
Frequency range 0.15 MHz ... 80 MHz
Fulfills EU RoHS substance requirements Yes
Height 130 mm
Hood version Polycarbonate
Housing material Plastic
Input 4 kV (Test Level 4 - asymmetrical)
Input 3 kV (Test Level 3 - symmetrical)
Input 6 kV (Test Level 4 - asymmetrical)
Input fuse 3.15 A (internal (device protection), slow-blow)
Input voltage range 2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range AC 3x 320 V AC ... 575 V AC
Input/Output asymmetrical
Inrush current integral (I 2 t) ≤ 0.25 A 2 s
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Insulation voltage input/output 3 kV AC (type test)
Insulation voltage input/output 1.5 kV AC (routine test)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Mains buffering time typ. 20 ms (400 V AC)
Mains buffering time typ. 20 ms (500 V AC)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Maximum altitude ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Maximum no-load power dissipation < 1 W (400 V AC)
Minimum order quantity 1 pc
Mounting position horizontal DIN rail NS 35, EN 60715
Mounting type DIN rail mounting
MTBF (IEC 61709, SN 29500) > 2300000 h (25 °C)
MTBF (IEC 61709, SN 29500) > 1300000 h (40 °C)
MTBF (IEC 61709, SN 29500) > 620000 h (60 °C)
Network type Star network
No-load proof yes
Nominal input voltage range 2x 400 V AC ... 500 V AC
Nominal output current (I N ) 5 A
Nominal power consumption 243.6 VA
Number of phases 3
Output 2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
Output 2 kV (Test Level 1 - asymmetrical)
Output characteristic U/I with dynamic load reserve
Output power 120 W
Output power 180 W (5 s)
Overvoltage category (EN 62368-1) II (≤ 2000 m)
Packing unit 1 pc
Product key CMPO33
Product type Power supply
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Protection class II (in closed control cabinet)
Protective circuit Transient surge protection; Varistor
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Rail applications EN 50121-4
Residual ripple ≤ 20 mV PP
Rise time ≤ 120 ms (U OUT (10 % ... 90 %))
Scip c8984056-a12f-4ca9-b03c-ae54d66267be
Setting range of the output voltage (U Set ) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Short-circuit-proof yes
Signal 1 kV (Test Level 2 - asymmetrical)
Signal 1 kV (Test Level 1 - symmetrical)
Signalization designation DC OK
SIL in accordance with IEC 61508 0
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, max. 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Standard - Electrical safety IEC 62368-1 (SELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standards/regulations EN 55016
Standards/regulations EN 61000-6-3 (Class B)
Standards/regulations EN 55011 (EN 55022)
Standards/regulations EN 61000-4-2
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Standards/regulations EN 61000-4-5
Standards/regulations EN 61000-4-6
Standards/regulations EN 61000-6-3
Status display LED
Stripping length 10 mm
Stripping length 8 mm
terminal blocks) V0
Test field strength 10 V/m (Test Level 3)
Type of housing Polycarbonate
Types of signaling LED
Types of signaling Floating signal contact
Typical national grid voltage 3x 480 V AC
Typical response time < 1 s
UL approvals UL Listed UL 508
UL approvals UL/C-UL Recognized UL 60950-1
UNSPSC 21.0 39121000
Weight per piece (excluding packing) 410.56 g
Weight per piece (including packing) 458.2 g
Width 35 mm
With protective coating no