Parcourir les categories
Phoenix Contact PSR-SCP- 24DC/ESD/4X1/30 relais de sécurité
Description
Phoenix Contact PSR-SCP- 24DC/ESD/4X1/30 fait partie de la gamme PSRclassic en tant que relais de sécurité. Il est spécifié pour les circuits d’arrêt d’urgence. Il se monte sur rail DIN et présente un indice de protection IP20.
Specifications
| Brand | Phoenix Contact |
|---|---|
| Model | PSR-SCP- 24DC/ESD/4X1/30 |
| Order Number | 2981800 |
| Inrush current | typ. 250 mA |
| Delay time range | 0.1 s ... 30 s ±30 % (adjustable) |
| Limiting continuous current | 6 A |
| Rated insulation voltage | 250 V |
| Sq. Total current | 120 A 2 (observe derating) |
| Switching voltage | max. 250 V AC/DC |
| Degree of protection | IP20 |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| REACH candidate substance (CAS No.) | 1-Methyl-2-pyrrolidone (NMP) (CAS: 872-50-4) |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
| Ambient temperature (operation) | -20 °C ... 45 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Application | Emergency stop |
| Application | Safety door |
| Application | Light grid |
| CO2e kg | 3.314 kg CO2e |
| Color (Housing) | yellow (RAL 1018) |
| Conductor cross-section AWG | 24 ... 12 |
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
| Connection method | Screw connection |
| Contact material | AgSnO 2 |
| Contact switching type | 4 enabling current paths |
| Control | 1 and 2 channel |
| Current consumption | typ. 3 mA |
| Current consumption | typ. 7 mA |
| Degree of pollution | 2 |
| Depth | 114.5 mm |
| ECLASS-13.0 | 27371819 |
| ECLASS-15.0 | 27371819 |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. |
| Error indication | K1/K2 and K3(t)/K4(t) LED, green |
| ETIM 10.0 | EC001449 |
| Exemption | 34, 7(a), 7(c)-I |
| Fulfills EU RoHS substance requirements | Yes |
| Height | 99 mm |
| Housing material | PA |
| Identification | CE-compliant |
| Inrush current | min. 25 mA |
| Inrush current | max. 6 A |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 288 W (48 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 90 W (110 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 88 W (220 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 1500 VA (250 V AC, τ = 0 ms) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible overall conductor resistance | 500 Ω (Input and reset circuit at U N ) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Maximum interrupting rating (inductive load) | 42 W (24 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 33 W (48 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 25 W (110 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 23 W (220 V DC, τ = 40 ms) |
| Maximum power dissipation for nominal condition | 25.8 W (U S = 26,4 V, I L ² = 120 A²) |
| Mechanical service life | approx. 10 7 cycles |
| Min. degree of protection of inst. location | IP54 |
| Minimum order quantity | 1 pc |
| Mounting position | any |
| Mounting type | DIN rail mounting |
| Nominal operating mode | 100% operating factor |
| Number of inputs | 2 |
| Number of outputs | 2 (undelayed: 13/14, 23/24) |
| Number of outputs | 2 (delayed: 37/38, 47/48) |
| Output fuse | 10 A gL/gG NEOZED (N/O contact) |
| Overvoltage category | II |
| Packing unit | 1 pc |
| Performance level (PL) | e |
| Pluggable | yes |
| Product key | DNA131 |
| Product type | Safety relays |
| Protective circuit | Suppressor diode |
| Rated control circuit supply voltage U S | 24 V DC -15 %; +10 % |
| Rated control supply current I S | typ. 75 mA |
| Rated surge voltage/insulation | 4 kV / basic insulation |
| Recovery time | 330 ms (Restart) |
| Recovery time | 1 s (Electric torque) |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Safety Integrity Level (SIL) | 3 |
| Scip | 96910064-e2e8-4429-9b05-cc7d43907774 |
| Screw thread | M3 |
| Set comprises | 1217839 PSR-SCP-24DC/ESD/4X1/30-SET35 |
| Shock | 15g |
| Status display | LED (green) |
| Stop category | 1 (delayed contacts) |
| Stop category (EN 60204-1) | 0 (Undelayed contacts) |
| Stripping length | 7 mm |
| Switching capacity | 3 A (24 V (DC 13)) |
| Switching capacity | 3 A (250 V (AC 15)) |
| Switching power | min. 0.4 W |
| Switching voltage | min. 15 V AC/DC |
| Typical release time | 20 ms (Undelayed contacts) |
| Typical release time | 100 ms (delayed contacts) |
| Typical response time | 150 ms (Monitored/manual and auto-start) |
| UNSPSC 21.0 | 39122200 |
| Weight per piece (excluding packing) | 170.97 g |
| Weight per piece (including packing) | 191.71 g |
| Width | 22.5 mm |