Specifications

Brand Phoenix Contact
Model PSR-ME40-4NO-2NC-24DC-SC
Order Number 1397654
Inrush current < 2.5 A (typ. with U S, Δt = 1 ms)
Switching frequency max. 0.5 Hz
Limiting continuous current 6 A (Observe derating and load limit curve)
Power consumption at U S typ. 1.85 W
Rated insulation voltage 250 V
Sq. Total current 72 A 2 (observe derating)
Switching voltage min. 10 V AC/DC
Delay time range 0.5 s ... 30 s ±40 %
Degree of protection IP20
Vibration (operation) 10 Hz ... 150 Hz, amplitude 0.35 mm, 2 g
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Ambient temperature (operation) -20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Application Extension module
CO2e kg 2.102 kg CO2e
Color (Housing) traffic gray B (RAL 7043)
Conductor cross-section AWG 24 ... 12
Conductor cross-section flexible 0.2 mm² ... 2.5 mm²
Conductor cross-section rigid 0.2 mm² ... 2.5 mm²
Connection method Screw connection
Contact material AgSnO 2
Contact switching type 4 enabling current paths
Contact switching type 2 N/C contacts in series
Control 1-channel
Current consumption typ. 14 mA
Degree of pollution 2
Depth 114.5 mm
Description of the input safety-related
Designation A1/A2
ECLASS-13.0 27371819
ECLASS-15.0 27371819
ECLASS-15.0 ASSET 27250101
Environment friendly use period (EFUP) EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC001449
Exemption 34, 7(a), 7(c)-I
Filter time 5 ms (in the event of voltage dips at U s )
Filter time 1 ms (Test pulse width of low test pulses)
Filter time 1 s (Test pulse rate for low test pulse)
Filter time No brightness test pulses / high test pulses permitted.
Fulfills EU RoHS substance requirements Yes
Height 112.2 mm
Housing material PA
Identification CE-compliant
Input current range "0" signal 0 mA ... 2 mA
Input voltage range "0" signal 0 V DC ... 5 V DC
Input voltage range "1" signal 20.4 V ... 26.4 V
Inrush current min. 10 mA
Inrush current max. 6 A
Inrush current max. 1 A
Limiting continuous current 1 A
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance 50 Ω
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Maximum altitude ≤ 2000 m (Above sea level)
Maximum power dissipation for nominal condition 17 W (U S = 26.4 V, I L ² = 72 A², P Total max = 2.6 W + 14.4 W)
Mechanical service life 10x 10 6 cycles
Min. degree of protection of inst. location IP54
Minimum order quantity 1 pc
Mounting position vertical or horizontal
Mounting type DIN rail mounting
Nominal operating mode 100% operating factor
Number of inputs 1
Number of outputs 4
Number of outputs 1
Operating voltage display 1 x LED (green)
Output description 2 N/O contacts each in series, safety-related, floating
Output description Diagnostic contact, 2 NC in series, floating
Output description 2 N/C contacts parallel, non-safety-related, floating
Output fuse 10 A gL/gG
Output fuse 4 A gL/gG (for low-demand applications)
Output fuse 1 A gL/gG
Output fuse 1 A (gL/gG)
Overvoltage category II, III (See the section “Insulation coordination”)
Packing unit 1 pc
Performance level (PL) d
Pluggable yes
Product key DN1113
Product type Safety relays
Protective circuit Reverse polarity protection; Suppressor diode
Protective circuit Suppressor diode
Rated control circuit supply voltage U S 24 V DC -15 % / +10 %
Rated control supply current I S typ. 77 mA (at U S )
Rated surge voltage/insulation See data sheet, section “Insulation coordination”.
Recovery time Delay time +500 ms
Relay type Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Restart time < 1 s (Boot time)
Safety Integrity Level (SIL) 2
Scip 967e1333-38e4-463d-884b-216d56534510
Screw thread M3
Set comprises 1397653 PSR-ME40-4NO-2NC-24DC-SC-SET35
Shock 15g
Sq. Total current 1 A 2
Status display 2 x LED (green)
Stop category (EN 60204-1) 1
Stripping length 7 mm
Switching capacity 5 A (AC 15)
Switching capacity 6 A (DC 13)
Switching capacity 1 A (AC 15)
Switching capacity 1 A (DC 13)
Switching power min. 100 mW
Switching voltage max. 250 V AC/DC
Tightening torque 0.5 Nm ... 0.6 Nm
Typical release time 50 ms (on demand via A1)
Typical response time typ. 40 ms (For U s autostart)
Weight per piece (excluding packing) 166.17 g
Weight per piece (including packing) 197.1 g
Width 22.5 mm