Phoenix Contact FL SWITCH 2214-2SFX fait partie de la gamme Managed Switch 2000 en tant que switch Ethernet industriel. Il se monte sur rail DIN et présente un indice de protection IP20.

Specifications

Brand Phoenix Contact
Model FL SWITCH 2214-2SFX
Order Number 1006188
HS Code 851762
Power supply connection via COMBICON, max. conductor cross-section 1.5 mm²
Supply voltage range 12 V DC ... 57 V DC
Signal contact control voltage typ. 24 V DC
Transmission speed 10/100 Mbps
Vibration A
Degree of protection IP20
Vibration (operation) in acc. with IEC 60068-2-6: 5g, 150 Hz
REACH candidate substance (CAS No.) Lead (CAS: 7439-92-1)
Shipbuilding approval Tested in accordance with IEC 60945 and IACS E10
Additional functions Transmission of MMS and GOOSE (IEC 61850-8-1)
Additional functions Transmission of Modbus/TCP
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Basic functions Store-and-forward switch, complies with IEEE 802.3
Certificate DEMKO 16 ATEX 1709X
Certificate IECEx ULD 16.0018 X
Certificate E366272
Certificate RU C-DE.HB49.B.00118/21
Certificate 2022122310115629
Color (Cover) light gray (RAL 7035)
Color (Housing) gray (RAL 7042)
Conductor cross-section AWG 24 ... 16
Conductor cross-section, flexible 0.25 mm² ... 1.5 mm²
Conductor cross-section, rigid 0.25 mm² ... 1.5 mm²
Conformance with EMC directives EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B
Conformance with EMC directives EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion A
Conformance with EMC directives EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A
Conformance with EMC directives EN 61000-6-2 EN 61000-4-5 (surge) Criterion A
Conformance with EMC directives EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A
Conformance with EMC directives EN 61000-6-2 EN 61000-6-4 (interference) Class A
Conformance with EMC directives EN 61000-6-2 EN 61000-6-4 (conducted interference) Class A
Connection method RJ45
Connection method SFP
Connection method Push-in spring connection
Current consumption 325 mA
Degree of pollution 2
Depth 119 mm
Diagnostic functions RMON History
Diagnostic functions LLDP (Link Layer Discovery Protocol)
Diagnostic functions SNMP-Traps
Diagnostic functions N:1-Portmirroring
Diagnostic functions ACD (Address Conflict Detection)
Diagnostic functions SysLog
Diagnostic functions CRC-Surveillance
ECLASS-13.0 19170401
ECLASS-15.0 19170401
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Emc B
Enclosure Required protection according to the Rules shall be provided upon installation on board
Environment friendly use period (EFUP) EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
ETIM 10.0 EC000734
Exemption 7(a), 7(c)-I
Filter functions Quality of Service (8 priority classes)
Filter functions Class of Service
Filter functions DiffServ/DSCP
Filter functions Port-Priorisierung
Filter functions IGMP Snooping/Querier (v1/v2)
Filter functions Auto-Query-Port
Filter functions Extended Multicast Filtering
Free from substances that could impair the application of coating Yes
Fulfills EU RoHS substance requirements Yes
Height 130 mm
Housing material Polycarbonate fiber reinforced
Humidity B
Identification  II 3 G Ex ec IIC T4 Gc
Identification Ex ec IIC T4 Gc
Identification cULus
Identification Class I, Division 2, Groups A, B, C, and D, T4
Identification Class I, Zone 2, AEx ec IIC T4
Identification Ex ec IIC T4 Gc X
Identification 2Ex e IIC T4 Gc X
Identification Install the device in a suitable, approved housing with at least IP66 protection.
Identification The operation of devices is permitted if all optical ports are connected or sealed with the supplied filler plugs.
Identification ISA S71.04.2013 G3 Harsh Group A
IP parameterization DHCP client
IP parameterization DHCP server (pool-based, port-based)
IP parameterization BootP
IP parameterization DCP (Discovery and Configuration Protocol)
Local diagnostics US1/2 Supply voltage US1, US2 Green LED
Local diagnostics FAIL Div. LED red
Local diagnostics LINK Link status Green LED
MAC address table 8k
Management Web-based management (HTTP/HTTPS)
Management Role-based user management (LDAP, RADIUS)
Management SNMPv1/v2/v3
Management Command Line Interface (Telnet, SSH)
Max. current consumption 1.6 A (U S = Min, T amb = Max, DO I = Max)
Maximum power dissipation for nominal condition 10.8 W (U S = Min, T amb = Max, DO I = Max)
Minimum order quantity 1 pc
Mounting type DIN rail mounting
Mttf 365.63 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
MTTF 218.22 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
MTTF 31.7 Years (SN 29500 standard, temperature 55°C, operating cycle 100%)
No. of channels 14 (RJ45 ports)
No. of channels 2 (SFP ports)
Noise immunity EN 61000-6-2
Number of interfaces 2
Output name Alarm output
Packing unit 1 pc
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Pluggable yes
Port security MAC-based, RADIUS (IEEE 802.1X), MAC Authentication Bypass
Product key DNN121
Product type Switch
PROFINET conformance class Conformance Class B
PROFINET device function PROFINET device
PROFINET device function Fast Startup
Protection class III (VDE 0106)
Redundancy MRP (Media Redundancy Protocol)
Redundancy RSTP (Rapid Spanning Tree Protocol)
Redundancy FRD (Fast Ring Detection)
Redundancy Large Tree Support
Redundancy LACP (Link Aggregation Control Protocol)
Redundancy PROFINET S2 system redundancy
Residual ripple 3.6 V PP (within the permitted voltage range)
Scip a60b5be3-00a6-4130-ac70-98e294379cdb
Shock (operation) 30g (EN 60068-2-27)
Signal delay ≥ 6.5 µs (Store and Forward mode, 10/100 Mbps, depending on the frame size)
Signal LEDs Data receive, link status
Special properties Extended temperature range
Special properties Development process certified in accordance with IEC 62443-4-1
Special properties Product certified in accordance with IEC 62443-4-2
Special properties The product is being prepared for compliance with the Cyber Resilience Act (CRA)
Standards/regulations EN 61000-6-4
Status and diagnostic indicators LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed)
Status display LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed)
Stripping length 9 mm
Supply voltage (DC) 24 V DC (redundant)
Temperature B
Test section 24 V supply / functional ground 500 V DC 1 min
Test section Ethernet interface/all other potentials 2.25 kV DC 1 min
Time synchronization SNTP (Simple Network Time Protocol)
Transmission length 100 m (per segment)
Transmission medium Copper
Transmission medium FO
Transmission physics Copper
Transmission physics Depending on the SFP module
Transmission speed 100 Mbps (full duplex)
Type Book type
Typical current consumption 325 mA (at U S = 24 V DC and 25 °C ambient temperature)
UNSPSC 21.0 43222600
Weight per piece (excluding packing) 470 g
Weight per piece (including packing) 582 g