Aller au contenu

Beckhoff EL2712 Terminal EtherCAT

Beckhoff EL2712 Terminal EtherCAT

Demander un devis

Quantite, etat et destination.

Demander un devis

Description

Le terminal EtherCAT Beckhoff EL2712 fournit 2 sorties TRIAC à contact à fermeture pour une tension de charge de 12…230 V CA.

Specifications

Brand Beckhoff
MPN EL2712
Max. output current 0.5 A per channel
Rotating field frequency 47…63 Hz
Peak current 40 A (16 ms), 1.5 A (30 s)
Rated load voltage 12…230 V AC
Residual voltage max. 1.5 V (60 mA…1 A), 150 Ω (< 60 mA)
Standby current 0.6 mA
Weight approx. 55 g
Operating temperature 0…55 °C
Storage temperature -25…+85 °C
Relative humidity 95%, no condensation
Surge voltage protection > 275 V
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings CE
Bit width in the process image 2 outputs
Configuration no address or configuration setting
Connection technology TRIAC output, 2-wire
Current consumption E-bus typ. 120 mA
Current consumption power contacts –
Distributed clocks –
Electrical isolation 500 V (E-bus/field voltage), 3750 V AC (1 min.)
Leakage current (OFF state) typ. 0.8 mA, max. 1.5 mA
Load type resistive, inductive
Number of outputs 2 x make contacts
Pluggable wiring level for all ESxxxx terminals
Protect. rating/installation pos. IP20/variable
Special features suitable for conventional blind motors
Switch-off time T/2
Switch-on time 0.1…10 ms, zero crossing
Switching times in zero crossing, 0.1…10 ms