Zum Inhalt springen

WAGO 787-832 Stromversorgung - Gebraucht

WAGO 787-832 Stromversorgung - Gebraucht

Angebot anfragen

Teilen Sie uns mit, was Sie benoetigen. Wir melden uns mit Informationen zu Verfuegbarkeit und Preisen.

Anfrage starten

Beschreibung

WAGO 787-832 Stromversorgung, 24 V. Modell 787-832 mit leichten Gebrauchsspuren.

Spezifikationen

Brand WAGO
Model 787-832
HS Code 850440
Origin Germany
ECCN NO US CLASSIFICATION
MTBF > 500,000 h (per IEC 61709)
boost 20A/4s; 60A/25ms
input 100-240Vac / 50-60 Hz
Width 57 mm / 2.244 inches
Height 163 mm / 6.417 inches
output 24Vdc (22-29.5Vdc) 10 A
Phases 1
PU (SPU) 1 pcs
UNSPSC 39,121,004
Weight 1472.2 g
Derating -3 %/K (> 50 °C)
ETIM 9.0 EC002540
TopBoost 60 ADC (25 ms)
Deviation ≤ 1 %
ETIM 10.0 EC002540
Signaling 1 x DC OK LED (green); 1 x Error LED (red); 1 x Stand-by input; 1 x DC OK relay contact (changeover contact)
eCl@ss 9.0 27-04-07-01
PowerBoost 20 ADC (4 s); 15 ADC (8 s)
eCl@ss 10.0 27-04-07-01
Strip length 8 … 9 mm / 0.31 … 0.35 inches
input_current 2.8-1.2 A
Internal fuse T 6.3 A / 250 VAC
Mounting type DIN-35 rail
Efficiency (typ.) 90 %
Inrush current ≤ 8 A (active power factor correction (PFC))
Strip length 5 … 6 mm / 0.2 … 0.24 inches
WAGO connector WAGO 231 Series
Connection type Input/output
Default Setting 24 VDC
Protection type IP20; per EN 60529
Residual ripple ≤ 70 mV (peak-to-peak)
Solid conductor 0.08 … 2.5 mm² / 28 … 12 AWG
Pollution degree 2
Protection class I
Series operation Yes
WAGO connector WAGO 733 Series
Climatic category 3K3 (per EN 60721)
Connection type Signaling
Overload behavior TopBoost/PowerBoost/Constant current mode
Pre-fuse (required) An external DC fuse is required for the DC input voltage.
Relative humidity 5 … 96 % (no condensation permissible)
Solid conductor 0.08 … 0.5 mm² / 28 … 20 AWG
Conformity marking CE
Current limitation 1.1 x Io nom (typ.)
Open-circuit-proof Yes
Parallel operation Yes
Input voltage range 1 x 85 … 264 VAC; 120 … 300 VDC
Nominal output power 240 W
Output voltage range 22 … 29.5 VDC (adjustable)
Overvoltage category II
Connection technology CAGE CLAMP®
Power loss Pl ≤ 0.8 W (standby); ≤ 3.8 W (no load); ≤ 24 W (nominal load)
RoHS Compliance Status Compliant,No Exemption
Backup fuse (recommended) Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic: B or C
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 12 AWG
Short-circuit-protected Yes
Isolation voltage (pri.-PE) 2.2 kVDC
Isolation voltage (sec.-PE) 0.7 kVDC
Standards/specifications EN 61010-1; EN 61010-2-201; EN 61204-3; EN 61558-2-16; UL 60950; UL 508
Fine-stranded conductor 0.08 … 0.5 mm² / 28 … 20 AWG
Input current Ii ≤ 1.2 A (240 VAC; 10 ADC)
Isolation voltage (pri.-sec.) 4.242 kVDC
Mains failure hold-up time ≥ 24 ms (230 VAC)
Operation status indicator Green LED (DC OK); Red LED (error)
Resistance to reverse feed ≤ 35 VDC
Ambient temperature (storage) -25 … +85 °C
Power factor correction (PFC) Active
Ambient temperature (operation) -25 … +70 °C (Device starts at -40 °C (type-tested))
Nominal mains frequency range 50 … 60 Hz; 0 Hz
Transient suppression (primary) Varistor
Depth from upper-edge of DIN-rail 179 mm / 7.047 inches
Nominal input voltage Ui nom 1 x 100 … 240 VAC
Nominal output current Io nom 10 A (24 VDC)