Kategorien durchsuchen
WAGO 2787-2146 - Gebraucht
Beschreibung
Gebrauchtes WAGO 2787-2146 Stromversorgungsmodul mit 24 VDC / 10 A Ausgang. Unterstützt 100-240 V~ Eingang mit IP20 Schutz.
Spezifikationen
| Brand | WAGO |
|---|---|
| MPN | 2787-2146 |
| HS Code | 850440 |
| Connection type | Input/output/signaling |
| Input Voltage | 100 ... 240 V~ |
| Input Frequency | 50 ... 60 Hz |
| Input Current | 2.7 ... 1.2 A |
| Inrush current | ≤ 11 A (after 1 ms) |
| Power factor correction (PFC) | Active |
| Power loss Pl | ≤ 1 W (standby); ≤ 2.2 W (no load); ≤ 12 W (230 VAC; nominal load) |
| Input voltage range | 1 x 90 … 264 VAC |
| Nominal mains frequency range | 50 … 60 Hz |
| Output voltage range | 24 … 28 VDC (adjustable) |
| Weight | 1063.3 g |
| Relative humidity | 5 … 96 % (no condensation permissible) |
| Ambient temperature (operation) | -25 … +70 °C (Device starts at -40 °C (type-tested)) |
| Ambient temperature (storage) | -40 … +85 °C |
| Backup fuse (recommended) | 16 A (for USA/Canada: 15 A) |
| Climatic category | 3K3 (per EN 60721) |
| Communications | EtherNet/IPTM (2789-9023 Communication Module); USB (750-923 Communication Cable); Ethernet/IP (2789-9023 Communication Module); IO-Link (2789-9080 Communication Module); Modbus RTU (Communication Module 2789-9015); Modbus TCP (2789-9052 Communication Module) |
| Conformity marking | CE |
| Connection technology | CAGE CLAMP® |
| Current limitation | 1.1 x Io nom (typ.) |
| Default Setting | 24 VDC |
| Depth from upper-edge of DIN-rail | 130 mm / 5.118 inches |
| Derating | -3 %/K (> 55 °C and Ui < 230 VAC); -3 %/K (> 60 °C and Ui ≥ 230 VAC) |
| Deviation | ≤ 1 % |
| Eccn | NO US CLASSIFICATION |
| Efficiency (typ.) | 95.2 % (230 VAC; 10 A; 25 °C) |
| ETIM 10.0 | EC002540 |
| ETIM 9.0 | EC002540 |
| Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 12 AWG |
| Fine-stranded conductor; with insulated ferrule | 0.25 … 1.5 mm² / 20 … 16 AWG |
| Fine-stranded conductor; with uninsulated ferrule | 0.25 … 2.5 mm² / 20 … 14 AWG |
| Fire load | 0.3 MJ |
| Height | 130 mm / 5.118 inches |
| Input current Ii | ≤ 1.2 A (240 VAC; Nominal load); ≤ 2.7 A (100 VAC; Nominal load) |
| Internal fuse | T 6.3 A / 250 VAC |
| Isolation voltage (pri.-PE, AC) | 2,200 V |
| Isolation voltage (pri.-sec., AC) | 3,510 V |
| Isolation voltage (sec.-PE) | 0.5 kVDC |
| Isolation voltage (sec.-signal) | 0.5 kVDC |
| Mains failure hold-up time | ≥ 25 ms (230 VAC) |
| Mounting type | DIN-35 rail |
| Mtbf | > 1,200,000 h (per IEC 61709) |
| Nominal input voltage Ui nom | 1 x 100 … 240 VAC |
| Nominal output current Io nom | 10 A (24 VDC) |
| Nominal output power | 240 W |
| Nominal output voltage Uo nom | 24 VDC (SELV) |
| Open-circuit-proof | Yes |
| Operating altitude (max.) | 5000 m |
| Output Connections | X2: 1 2 3 4 5 |
| Output Power | 240 W |
| Overload behavior | TopBoost/PowerBoost/Time-limited constant current mode (other overload behaviors can be set) |
| Overvoltage category | III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.) |
| Overvoltage protection; secondary | Internal protective circuit; ≤ 35 VDC (in the event of a fault) |
| Parallel operation | Yes |
| Phases | 1 |
| Pollution degree | 2 |
| Powerboost | 15 ADC (5 s) |
| Protection class | I |
| Protection Rating | IP20 |
| Protection type | IP20; per EN 60529 |
| PU (SPU) | 1 pcs |
| Residual ripple | ≤ 70 mV (peak-to-peak) |
| Resistance to reverse feed | ≤ 35 VDC |
| RoHS Compliance Status | Compliant,No Exemption |
| Series operation | Yes |
| Short-circuit-protected | Yes |
| Signaling | Optical status indication (DC OK; load; warning and error states); Digital signal input and output (DI/DO) |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 12 AWG |
| Standards/specifications | UL 121201 (HazLoc); EN 61010-2-201; EN 61204-3; UL 61010-1; UL 61010-2-201; SEMI F47 |
| Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
| Topboost | Up to 600 % |
| Transient suppression (primary) | Yes |
| Unspsc | 39,121,004 |
| WAGO connector | WAGO 721 Series |
| Width | 50 mm / 1.969 inches |