Zum Inhalt springen

B&R X20 AI4622 - Neu

B&R X20 AI4622 - Neu

Angebot anfragen

Menge, Zustand und Zielort angeben.

Angebot anfragen

Beschreibung

B&R X20AI4622 Modul, hergestellt in Österreich, neu.

Spezifikationen

Brand B&R
Model X20 AI4622
MPN X20AI4622
Origin Austria
Current INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Common-mode range ±12 V
Current 0 to 20 mA = 0.009 %/°C 4 to 20 mA = 0.0113 %/°C
Current 0 to 20 mA = 0.004 %/°C 4 to 20 mA = 0.005 %/°C
Current Max. ±50 mA
Current 12-bit
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
Voltage 0.006%/°C
Voltage 0.002%/°C
Voltage Max. ±30 V
Voltage ±12-bit
Voltage 20 MΩ
Input protection Protection against wiring with supply voltage
ABS Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
B&R ID code 0x1BAA
Bus 0.01 W
BV EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
CCS Yes
CE Yes
Channel type Yes, using software
Common-mode rejection 70 dB
Conversion procedure SAR
Conversion time 400 μs for all inputs
CRA (Cyber Resilience Act) In preparation
DC 70 dB
Electrical isolation Channel isolated from bus Channel not isolated from channel
Gain 0 to 20 mA = 0.08% / 4 to 20 mA = 0.1%
Gain 0.08%
HazLoc cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Horizontal Yes
Horizontal mounting orientation -25 to 60°C
Input ±10 V or 0 to 20 mA / 4 to 20 mA, via different terminal connections
Input filter Third-order low-pass filter / Cutoff frequency 1 kHz
Input type Differential input
Inputs Yes, using LED status indicator and software
Installation elevation above sea level Reduction of ambient temperature by 0.5°C per 100 m
Installation elevation above sea level No limitation
Installation elevation above sea level IP20
Insulation voltage between channel and bus 500 V eff
Internal I/O 1.1 W
KC Yes
KR Yes
LR ENV1
Module run/error Yes, using LED status indicator and software
Offset 0 to 20 mA = 0.03% / 4 to 20 mA = 0.0375%
Offset 0.015%
Operation 5 to 95%, non-condensing
Output format INT
Output of digital value during overload Configurable
Pitch 12.5 +0.2 mm
Status indicators I/O function per channel, operating state, module status
Storage -40 to 85°C
Storage 5 to 95%, non-condensing
Transport -40 to 85°C
Transport 5 to 95%, non-condensing
UKCA Yes
UL cULus E115267 Industrial control equipment
Vertical Yes
Vertical mounting orientation -25 to 50°C